Goodmans GPC 13 SEER R-410A ELECTRICAL DATA *Blower Only, Heat Mode, Product Design, GPC1324H41

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 8
Image 8
ELECTRICAL DATA (*Blower Only, Heat Mode)

PRODUCT DESIGN

 

 

 

 

GPC13[24-60]H41**

ELECTRICAL DATA (*Blower Only, Heat Mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit #1

 

Circuit #2

 

Model and

Minimum Circuit

Maximum

Minimum Circuit

Maximum

Actual

Overcurrent

Overcurrent

kW & BTU

Heat Kit Usage

Ampacity

 

Ampacity

 

 

Protection (amps)

 

Protection (amps)

at 240V

 

at 208 / 240V

 

at 208 / 240V

 

 

 

at 208 / 240V

 

at 208 / 240V

 

 

 

 

 

 

 

 

GPC1324H41*

 

 

 

--

--

 

--

--

HKR05*,C*

24

/ 27

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

33

/ 38

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

45

/ 51

 

60 / 60

--

 

--

9.5 / 32,400

GPC1330H41*

2.4

/ 2.4

 

--

--

 

--

--

HKR05*,C*

24

/ 27

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

34

/ 39

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

45

/ 52

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

45

/ 52

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

GPC1336H41*

 

 

 

--

--

 

--

--

HKR05*,C*

24

/ 27

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

34

/ 39

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

45

/ 52

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

45

/ 52

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

GPC1342H41*

 

 

 

--

--

 

--

--

HKR05*,C*

25

/ 27

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

34

/ 39

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

46

/ 52

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

46

/ 52

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

HKR20*,C*

46

/ 52

 

60 / 60

43 / 49

 

60 / 60

19.5 / 66,500

GPC1348H41*

 

 

 

--

--

 

--

--

HKR05*,C*

25

/ 28

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

34

/ 40

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

46

/ 53

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

46

/ 52

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

HKR20*,C*

46

/ 52

 

60 / 60

43 / 49

 

60 / 60

19.5 / 66,500

GPC1349H41*

 

 

 

--

--

 

--

--

HKR05*,C*

25

/ 28

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

34

/ 40

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

46

/ 53

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

46

/ 52

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

HKR20*,C*

46

/ 52

 

60 / 60

43 / 49

 

60 / 60

19.5 / 66,500

GPC1360H41*

 

 

 

--

--

 

--

--

HKR05*,C*

26

/ 30

 

30 / 30

--

 

--

4.75 / 16,200

HKR08*,C*

36

/ 40

 

40 / 40

--

 

--

7.0 / 23,800

HKR10*,C*

48

/ 54

 

60 / 60

--

 

--

9.5 / 32,400

HKR15*,C*

48

/ 54

 

60 / 60

22 / 25

 

30 / 30

14.25 / 48,600

HKR20*,C*

48

/ 54

 

60 / 60

43 / 49

 

60 / 60

19.5 / 66,500

IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.

All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent

protection during refrigeration cycle.

8

Page 8
Image 8
Goodmans GPC 13 SEER R-410A ELECTRICAL DATA *Blower Only, Heat Mode, Product Design, GPC1324-60H41, GPC1324H41, GPC1330H41

FAQ

What is the minimum circuit ampacity for GPC1324H41A model?

The minimum circuit ampacity for the GPC1324H41A model is 24A.

Is a separate power supply required for the HKR heater kit?

Yes, a separate power supply is required for the HKR heater kit.

What precautions should be taken regarding wire size for electric heaters?

All wires and overcurrent protection devices should be sized for use with electric heaters only, and without refrigeration. If heaters are not installed with the correct wire size, overheating and fire could occur.