Goodmans GPC1324H41A PACKAGE COOLING SPECIFICATIONS GPC1324-36H41AB, MODELS WITH 5MM COILS, Unit

Models: GPC1324H41A GPC 13 SEER R-410A

1 47
Download 47 pages 14.36 Kb
Page 31
Image 31
PACKAGE COOLING SPECIFICATIONS GPC13[24-36]H41AB

PACKAGE COOLING SPECIFICATIONS GPC13[24-36]H41AB

MODELS WITH 5MM COILS

 

 

GPC1324H41AB

GPC1330H41AB

GPC1336H41AB

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

24,000

28,600

36,000

CAPACITY

SEER

13.0

13.0

13.0

 

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

208-230/1/60

208-230/1/60

ELECTRICAL

AMPS (TOTAL)

16.1

15.76

20.06

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

19.5

19

24.2

 

MAXIMUM OVERCURRENT PROTECTION (1)

30

30

40

COMPRESSOR

TYPE

SCROLL

SCROLL

SCROLL

 

RATED LOAD AMPS

13.5

12.8

16.7

 

LOCKED ROTOR AMPS

58.3

64

79

 

 

 

 

 

CONDENSER

HORSEPOWER

1/6

1/6

1/4

FAN MOTOR

RPM

815

815

830

 

FULL LOAD AMPS

1.1

1.1

1.5

 

LOCKED ROTOR AMPS

1.7

1.7

3.0

 

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) /# OF BLADES

22 / 2

22 / 2

22 / 4

 

 

 

 

 

CONDENSER

FACE AREA - SQ. FT.

12.3

12.3

12.3

COIL

NUMBER OF ROWS

1

1

1

 

FINS PER INCH

26

26

26

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

1/4 - 3

1/3 - 3

1/3 - 3

BLOWER

FULL LOAD AMPS

1.5

1.86

1.86

MOTOR

LOCKED ROTOR AMPS

2.2

3.2

3.2

 

MOTOR SPEED TAP - COOLING

MEDIUM

LOW

LOW

 

RPM

1075

1075

1075

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

9 x 6

9 x 6

9 x 8

BLOWER

RATED SCFM COOLING

815

1,080

1,205

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

0.5

 

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

4.6

4.6

5.2

COIL

NUMBER OF ROWS

3

3

3

 

FINS PER INCH

14

14

14

 

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

20 x 20 x 1

20x 25 x 1

25 x 25 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

3/4"

 

EXPANSION DEVICE

ORIFICE (0.057)

ORRIFICE (0.062)

ORIFICE (0.068)

 

REFRIGERANT CHARGE R-410A (Oz.)

63

62

61

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.

3/4, 1, 1-1/4

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

1/2

1/2

 

SHIPPING WEIGHT LBS.

290

290

370

 

OPERATING WEIGHT LBS.

280

280

360

 

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

31

Page 31
Image 31
Goodmans PACKAGE COOLING SPECIFICATIONS GPC1324-36H41AB, MODELS WITH 5MM COILS, GPC1324H41AB, GPC1330H41AB, Cooling

FAQ

What type of compressor does the GPC1324H41AB model have?

The GPC1324H41AB model comes with a scroll compressor.

What is the SEER rating of the GPC1336H41AB model?

The SEER rating of the GPC1336H41AB model is 13.0.

How should the unit be electrically connected?

It is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.