Maintain and inspect the generator, air compressor, and other equipment per the manufacturer recommendations to avoid an unexpected shutdown. Unexpected equipment shutdown will cause voltage fluctuations that can damage electrical equipment.

Use a wall power supply with enough cur- rent to meet system requirements. Failure to do so will cause voltage fluctuations that can damage electrical equipment.

3.Electrical requirements See Table 1.

Installing this equipment requires access to parts which may cause electric shock or other serious injury if work is not performed properly. Have a qualified electrician connect power and ground to main power switch ter- minals, see page 25. Be sure your installa- tion complies with all National, State and Local safety and fire codes.

Table 1: Electrical Requirements

(kW/Full Load Amps)

 

 

 

Full

 

 

 

 

Load

 

 

 

Voltage

Peak

System

Part

Model

(phase)

Amps*

Watts**

 

 

 

 

 

253400

H-40

230V (1)

100

23,100

253401

H-40

230V (3)

71

26,600

253402

H-40

400V (3)

41

26,600

253403

H-XP3

230V (1)

100

23,100

253404

H-XP3

230V (3)

95

31,700

253405

H-XP3

400V (3)

52

31,700

 

 

 

 

Setup

Table 1: Electrical Requirements

 

(kW/Full Load Amps)

 

 

 

 

 

 

 

 

 

 

 

Full

 

 

 

 

 

Load

 

 

 

 

Voltage

Peak

System

 

Part

Model

(phase)

Amps*

Watts**

 

 

 

 

 

 

 

253407

H-40

230V (3)

95

31,700

 

253408

H-40

400V (3)

52

31,700

 

255400

H-25

230V (1)

69

15,960

 

255401

H-25

230V (3)

46

15,960

 

255402

H-25

400V (3)

35

15,960

 

255403

HXP2

230V (1)

100

23,260

 

255404

HXP2

230V (3)

59

23,260

 

255405

HXP2

400V (3)

35

23,260

 

255406

H-25

230V (1)

100

23,260

 

255407

H-25

230V (3)

59

23,260

 

255408

H-25

400V (3)

35

23,260

 

253725

H-50

230V (1)

100

23,100

 

253726

H-50

230V (3)

71

26,600

 

253727

H-50

400V (3)

41

26,600

 

256505

H-50

230V (3)

95

31,700

 

256506

H-50

400V (3)

52

31,700

 

*Full load amps with all devices operating at maximum capabilities. Fuse requirements at various flow rates and mix chamber sizes may be less.

**Total system watts, based on maximum hose length for each unit:

Parts 255400 through 255408, 310 ft (94.6

m)maximum heated hose length, including whip hose.

Parts 253400 through 253408, 410 ft (125

m)maximum heated hose length, including whip hose.