Integrated Flow Control
Flow Control Troubleshooting
Problem: Flow Command does not produce fluid output.
Test the system as follows, to determine if the problem is mechanical or electrical.
1.Install a
a.For module 249849: Remove the plug from the 1/8 npt(f) air gauge port and install the gauge. See FIG. 71 on page 67.
b.For module 24H989: Install a 1/8 npt(m) x 1/8 npt (fbe) tee in the air outlet port. Install the gauge in one branch of the tee and the air outlet fitting in the other. See FIG. 72 on page 67.
2.Set the system to Manual Override, % Open mode; see steps
3.Set the % Open value to 50. See FIG. 90.
Set % Open value to 50
50
FIG. 90. Set % Open to 50 Percent
4.Ensure that the gun is triggered. Increase the % Open value on the EasyKey, then decrease. The gauge reading should also increase then decrease.