SECTION 2: CIRCUIT REQUIREMENTS
220V | 440V | |
|
|
|
Serious personal injury could occur if you connect your machine to the power source before you have completed the set up pro- cess. DO NOT connect the machine to the power source until instructed to do so.
Wiring
The Model G0503 is prewired for 220V
Amperage Draw
The Model G0503 has a 20 HP main motor and a 2 HP hydraulic pump motor that will draw the following amps at 220V
Main Motor | 48 | Amps |
Hydraulic Pump Motor | 6 | Amps |
Circuit Breaker Requirements
Install the machine on a dedicated circuit to reduce the possibility of overloading the circuit and tripping the circuit breaker. If the circuit breaker trips and the circuit is of the correct load capacity, have the circuit inspected by a qualified electrician. Never use a larger circuit breaker than stated below, or you will increase the risk of fire.
Circuit Breaker | 60 Amp |
Minimum Wire Requirements |
|
For 220V
Wire | 6 GA. Copper |
We recommend running THWN/THHN grade insulated wire through rigid conduit and hardwir- ing into a locking power disconnect. Consult a qualified electrician for information on local and national electrical codes.
Serious personal injury could occur if you connect your machine to the power source before you have completed the setup pro- cess. DO NOT connect the machine to the power source until instructed to do so.
Wiring
The Model G0503 is prewired for 220V
Amperage Draw
The Model G0503 has a 20 HP main motor and a 2 HP hydraulic pump motor that will draw the following amps at 440V
Main Motor | 24 | Amps |
Hydraulic Pump Motor | 3 | Amps |
Circuit Breaker Requirements
Install the machine on a dedicated circuit to reduce the possibility of overloading the circuit and tripping the circuit breaker. If the circuit breaker trips and the circuit is of the correct load capacity, have the circuit inspected by a qualified electrician. Never use a larger circuit breaker than stated below, or you will increase the risk of fire.
Circuit Breaker.........................................30 Amp
Minimum Wire Requirements
For 440V
Wire | 10 GA. Copper |
We recommend running THWN/THHN grade insulated wire through rigid conduit and hardwir- ing into a locking power disconnect. Consult a licensed electrician for information on local and national electrical codes.
Model G0503 (Mfg. Since 12/08)