Harman Stove Company HB 38 DV manual Venting, into a wallor siding

Models: HB 38 DV

1 46
Download 46 pages 46.8 Kb
Page 23
Image 23
into a wallor siding.

Only For Qualified Installers

VENTING

Requirements for Terminating the Venting WARNING:Ventingterminalsmust notberecessed

into a wallor siding.

In addition, the following must be observed: A. The clearance above grade, or a veranda, porch, deck or balcony must be a minimum of 12" (30

cm).1

B. The clearance to a window or door that may be opened must be a minimum of 12" (30 cm).1

C. A12" (30cm) clearanceto apermanently closed window is recommended to prevent condensation on the window.

D. The vertical clearance to a ventilated soffit lo- cated above the terminal within a horizontaldistance of 2 feet (60 cm) from the center-line of the terminal must be a minimum of 18" (46 cm).

E. The clearance to an unventilated soffit must be a minimum of 12" (30 cm).

F. The clearance to an outside corner is 11" from center of pipe.

G. The clearance to an inside corner is 12" (30

cm).

H.A vent must not be installed within 3 feet (90 cm) above a meter/regulator assembly when measured from the horizontalcenter-line of the regulator.1

I.The clearance to service regulator vent outlet

must be a minimum of 6 feet (1.8 m).1

J.The clearance to a non-mechanical air supply inlet to the building or the combustion air inlet to any other appliance must be a minimum of 12 inches (30 cm).1

K.The clearance to a mechanical air supply inlet must be a minimum of 6 feet (1.8 m).1

L.The clearance above a paved sidewalk or a paved driveway located on public property must be a minimum of 7 feet (2.1 m).1,2

M. The clearance under a veranda, porch, deck or balcony must be a minimum of 12 inches (30 cm).1,3 1As specified in CAN 1 B1-149Installation Codes (current edition). Note: Localcodes orregulations may

require different clearances.

2A vent shall not terminate directly above a side- walk or paved driveway which is located between two single family dwellings and serves both dwellings.

3Only permitted if veranda, porch, deck, or bal- cony is fully open on a minimum of 2 sides beneath the floor.

I nside

Corner

Det ail

V

= Vent terminal

Fixed

 

 

Closed

Openable

Fixed

Openable

 

Closed

 

 

A = Air supply inlet

= Area where terminal is not permitted

23

Page 23
Image 23
Harman Stove Company HB 38 DV manual Venting, into a wallor siding