Heat & Glo • Soho-CE • 2111-900 Rev. D • 6/07
18
8
8 Installing Flue Pipe

Figure 8.1 Adding Flue Components
Install Support Brackets
For Horizontal Runs - The ue system must be supported
every 1.5 meters of horizontal run by a horizontal pipe
support.
To install support brackets for horizontal runs:
• Place the pipe supports around the ue pipe.
• Nail the pipe supports to the framing members.
For Vertical Runs - The ue system must be supported
every 2.4 meters above the appliance ue outlet by wall
brackets. To install support brackets for vertical runs:
• Attach wall brackets to the ue pipe and secure the wall
bracket to the framing members with nails or screws.
Attach the First Flue Component to Starting Collars
To attach the rst ue component to the starting collars
of the appliance:
• Lock the flue components into place by sliding the
concentric pipe sections with four (4) equally spaced
interior beads into the appliance collar or previously
installed component end with four (4) equally spaced
indented sections.
When the internal beads of each outer pipe line up, rotate
the pipe section clockwise about one-quarter (1/4) turn
(see Figure 8.1). The ue pipe is now locked together.
Slide the ceramic rope ring over the rst ue section and
place it ush to the appliance. This will prevent cold air
in ltration. High temp caulk may be used to hold the part
in place. Continue to add ue components.
Continue Adding Flue Components
Continue adding flue components, locking each
succeeding component into place.
Ensure that each succeeding ue component is securely
tted and locked into the preceding component.
• 90° elbows may be installed and rotated to any point
around the preceding component’s vertical axis. If an
elbow does not end up in a locked position with the
preceding component, attach with a minimum of two (2)
sheet metal screws.
Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
• Ensure ue components are locked together correctly.
Pipe may separate if not properly joined.
Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use ue run supports per installation instructions.
Connect ue sections per installation instructions.
Maintain all clearances to combustibles.
Do NOT allow �� ue to sag below connection point
to appliance.
Improper support may allow ue to sag or separate.

A. Assembly of Flue Sections

WARNING
WARNING