Heat & Glo • Soho-CE • 2111-900 Rev. D • 6/07 9
Electrical
Service
V
S
VS
V
T
D*
V
M
N
P
R
Q
V= VENT TERMINAL X= AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTED
Figure 4.4 Minimum Clearances for Termination
A = 31 cm ....................clearances above grade, veranda,
porch, deck or balcony
B = 31 cm ....................clearances to window or door
that may be opened, or to perma-
nently closed window. (Glass)
D* = 31 cm ....................vertical clearance to unventilated
sof t or to ventilated sof t located
above the terminal
76 cm .....................for vinyl clad sof ts and below
electrical service
F = 23 cm ...................clearance to outside corner
G = 15 cm ....................clearance to inside corner
H = 91 cm ....................not to be installed above a gas
meter/regulator assembly within 90
cm horizontally from the center-line
of the regulator
I = 1.8 m .....................clearance to gas service regulator
ue outlet
J = 31 cm ......................clearance to non-mechanical
air supply inlet to building or the
combustion air inlet to any other
appliance
K = 1.8 m .......................clearance to a mechanical
(powered) air supply inlet
L** = 2.1 m .......................clearance above paved
sidewalk or a paved driveway
located on public property
m*** = 46 cm ......................clearance under veranda, porch,
deck, balcony or overhang
1.1 m ......................vinyl
** a ue shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the oor, or meets Note 2.
NOTE 1: On private property where termination is less than 7 feet above
a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See ue components page)
NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions speci ed for vinyl
or non-vinyl siding and sof ts. 1. There must be 2.7 m minimum between
termination caps. 2. All mechanical air intakes within 3M of a termination
cap must be a minimum of 2.7 m below the termination cap. 3. All gravity
air intakes within 2.7 m of a termination cap must be a minimum of .31M
foot below the termination cap.
(See Note 1)
(See Note 1)
(See Note 2)
NOTE 3: Local codes or regulations may require different
clearances.
NOTE 4: Termination caps may be hot. Consider their proximity to
doors or other traf c areas.
NOTE 5: Location of the ue termination must not interfere with
access to the electrical service.
Heat & Glo assumes no responsibility for the improper performance
of the appliance when the ueing system does not meet these
requirements.
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
Alcove Applications
S = 15 cm .......................clearance from sides of elec-
trical service
T = 31 cm ........................clearance above electrical
service
(See Note 5)
(See Note 5)
See Notes 3 & 4
QMIN RMAX
1 cap .91 m 2 x Q ACTUAL
2 caps 1.8 m 1 x Q ACTUAL
3 caps 2.7 m 2/3 x Q ACTUAL
4 caps 3.7 m 1/2 x Q ACTUAL
N = 15 cm .....................non-vinyl sidewalls
31 cm .....................vinyl sidewalls
P = 2.4 m