See note 2

See note 3

T

 

T = Flue terminal

M = Gas meter

Shading indicates prohibited

 

I = Mechanical air inlet

P = Electricity meter or fuse box

areas for flue terminals

a

- Below eaves, balconies or other projections:

MIN. CLEARANCE - in. (mm)

 

Appliances up to 50 MJ/h input

12

(300)

 

Appliances over 50 MJ/h input

................................................................................

20-1/2

(500)

b

- From the ground or above a balcony

12

(300)

c

- From a return wall or external corner

20-1/2

(500)

d

- From a gas meter (M)

39

(1000)

e

- From an electricity meter or fuse box (P)

20-1/2

(500)

f

- From a drain or soil pipe

6

(150)

g- Horizontally from any building structure (unless appliance approved

for closer installation) or obstruction facing a terminal

20-1/2

(500)

h - From any other flue terminal, cowl, or combustion air intake

20-1/2

(500)

j- Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building, with the exception of

sub-floor ventilation:

 

 

Appliances up to 150 MJ/h input

20-1/2

(500)

Appliances over 150 MJ/h input

60

(1500)

k - From a mechanical air inlet, including a spa blower

60

(1500)

n- Vertically below an openable window, non-mechanical air

inlet or any other opening into a building, with the exception of

See table

sub-floor ventilation

 

 

below

 

 

 

 

 

CLEARANCE

 

Space Heaters

 

All other appliances

 

 

 

 

 

Up to 50 MJ/h input

Up to 50 MJ/h input

Over 50 MJ/h input and

Over 50 MJ/h input

Up to 150 MJ/h input

 

 

 

6 in. (150 mm)

20 in. (500 mm)

39 in. (1000 mm)

59 in. (1500 mm)

 

 

 

 

NOTES: 1. All distances are measured vertically or horizontally along the wall to a point in line with the nearest part of the terminal.

2.Prohibited area below electricity meter or fuse box extends to ground level.

3.See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.

4.See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue

terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.

MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS

OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES

Figure 6.3 Minimum Clearances for Termination

Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF2079-980 Rev. N • 5/12

25