Heat & Glo LifeStyle 550TRSI-AUF Top Vent - Horizontal Termination, V1 Minimum, H1 Maximum

Models: 550TRSI-AUF

1 80
Download 80 pages 27.78 Kb
Page 27
Image 27
Top Vent - Horizontal Termination

Top Vent - Horizontal Termination

V1 Minimum

H1 Maximum

Elbow only

NOT ALLOWED

1 ft.

305 mm

2 ft.

610 mm

2 ft.

610 mm

4 ft.

1.22 m

3 ft.

914 mm

8 ft.

2.44 m

4 ft.

1.22 m

10 ft.

3.05 m

5 ft.

1.52 m

16 ft.

4.88 m

V1 + H1 = 30 ft. (9.14 m) Maximum

Note: A 6 in. (152 mm) section of straight flue must be attached to the heater before a 90° elbow.

USE SLP SERIES COMPONENTS ONLY

V1 Minimum WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

• Install wall shield and ceiling firestops as speci- fied.

Failure to keep insulation or other material away from vent pipe may cause fire.

Example: DVP pipe 3 ft. (1 m) min. vertical = 11 ft. (3.35 m) max. horizontal

SLP pipe 7 ft. (2.13 m) min. vertical = 11 ft. (3.35 m) max. horizontal

H1

V1

Figure 7.4

Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF2079-980 Rev. N • 5/12

27

Page 27
Image 27
Heat & Glo LifeStyle 550TRSI-AUF Top Vent - Horizontal Termination, Use Slp Series Components Only, V1 Minimum, H1 Maximum