Heat & Glo LifeStyle 550TRSI-AUF Vent Clearances and Framing, A. Pipe Clearances to Combustibles

Models: 550TRSI-AUF

1 80
Download 80 pages 27.78 Kb
Page 38
Image 38
8 Vent Clearances and Framing

8 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

B. Wall Penetration Framing

 

 

WARNING! Risk of Fire! Maintain air space clearance to

Combustible Wall Penetration

 

 

vent. DO NOT pack insulation or other combustibles:

Whenever a combustible wall is penetrated, you must

 

 

 

 

Between ceiling firestops

 

frame a hole for the wall shield firestop(s). The wall shield

Between wall shield firestops

firestop maintains minimum clearances and prevents cold

• Around vent system

 

air infiltration.

 

 

 

 

 

Failure to keep insulation or other material away from

• The opening must be framed on all four sides using the

vent pipe may cause over heating and fire.

same size framing materials as those used in the wall

 

 

 

 

construction.

 

 

 

 

 

 

 

 

 

• DVP pipe - A wall shield firestop is required on one side

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

only on interior walls. If your local inspector requires a

DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184

wall shield firestop on both sides, then both wall shield

 

mm) thick.

 

 

• If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If

firestops

must

have

a heat

shield

(refer

to Section

 

wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

16.B.) attached to them.

 

 

 

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

 

 

 

 

194 mm thick).

 

 

• SLP pipe - A wall shield firestop must be placed on each

• If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed.

 

If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

side of an interior wall. A minimum 1-1/2 inch (38 mm)

 

 

 

 

overlap of attached heat shields must be maintained.

 

 

(DVP-SLP Pipe Shown)

• See Section 10.H. for information for regarding the in-

 

 

 

 

stallation of a horizontal termination cap.

 

 

 

Heat

3 in. (76 mm)

Non-Combustible Wall Penetration

 

 

 

3 in. (76 mm)

Shield

top clearance *

If the hole being penetrated is surrounded by noncom-

 

top clearance

 

Heat

 

 

 

Shield

bustible materials such as concrete, a hole with diameter

 

 

 

 

 

 

 

 

 

 

1 in. (25 mm)

 

 

one inch greater than the pipe is acceptable.

 

clearance around

 

 

Whenever a non-combustible wall is penetrated, the wall

vertical sections

 

 

 

 

 

1 in. (25 mm)

shield firestop is only required on one side and no heat

 

 

Wall

clearance

shield is necessary.

 

 

 

 

 

 

Shield

bottom & sides

 

 

 

 

 

 

Firestop

 

 

 

 

 

 

 

 

 

 

WALL

Note: A 6 in. (152 mm) section of straight flue must

 

 

 

be attached to the fireplace before a 90° elbow.

 

 

 

 

 

 

Heat

3 in. (76 mm)

 

 

 

 

 

 

 

 

 

Shield

top clearance *

 

 

 

 

 

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

Shield

 

 

 

 

 

 

 

 

 

Wall

1 in. (25 mm)

 

 

 

 

 

 

 

 

 

clearance

 

 

 

 

 

 

 

 

 

Shield

bottom & sides

 

 

 

 

C

 

 

 

 

Firestop

 

10 in.

 

10 in.

 

 

 

 

 

 

 

 

D

 

 

 

 

 

WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* When using SLP or SL-D pipe, minimum clearances from the vent pipe to combus-

 

10 in.

 

12 in.

 

 

 

 

tible materials at inside wall firestops are: Top: 2-1/2 in. (64 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom: 1/2 in. (13 mm)

 

 

 

 

 

 

 

 

 

 

Sides: 1 in. (25 mm)

 

 

 

 

 

 

 

Figure 8.1 Horizontal Venting Clearances To Combustible

A*

B*

 

 

 

 

 

 

Materials

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A*

B*

C

D

 

 

 

 

550TRSI-AUF

in.

40-3/4 24-3/8 39-3/4

23-3/8

 

 

 

 

550TRSILP-AUF

mm

1035

619

1010

593

 

 

 

 

* Shows center of vent framing hole for top or rear venting. The center of the

 

 

 

 

hole is 1 in. (25 mm) above the center of the horizontal vent pipe.

 

 

 

 

Figure 8.2

Wall Penetration

 

 

 

38

 

 

Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF2079-980 Rev. N • 5/12

 

 

 

 

 

 

 

 

 

Page 38
Image 38
Heat & Glo LifeStyle 550TRSI-AUF owner manual Vent Clearances and Framing, A. Pipe Clearances to Combustibles