Heat & Glo LifeStyle 6000GCF-IPI D. Vent Diagrams, Top Vent - Horizontal Termination One Elbow

Models: 6000GCF-IPI 6000GCF-IPILP

1 56
Download 56 pages 39.21 Kb
Page 13
Image 13
D. Vent Diagrams

D. Vent Diagrams

Note: The 6000 series fireplaces can adapt to SL series vent pipe, if desired.

When venting off the top of the unit, use a DVP-2SLadapter and a minimum 48 inch vertical section of SL series vent pipe.

After the 48 inch vertical section, the venting table rules must be followed. The first 48 inch vertical section is NOT counted as part of the vertical components in the table. It is still counted as part of the overall maximum run. All venting table rules for the vent run must still be followed.

Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal SL pipe 7 ft. min. vertical = 11 ft. max. horizontal

1.Top Vent - Horizontal Termination One Elbow

V1

H1

Figure 5.3

1.Top Vent - Horizontal Termination One Elbow WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

WARNING

Fire Risk.

When using DVP-HRC-SS and DVP-HRC-ZC- SS termination caps on top vented fireplaces, a 6 inch minimum vertical vent section is required before installing first elbow.

V1 Minimum

H1

Maximum

6 inches

152 mm

3 ft

 

914 mm

1 ft

305 mm

3 ft

 

914 mm

 

 

 

 

 

2 ft

610 mm

6 ft

 

1.8 m

 

 

 

 

 

3 ft

914 mm

9 ft

 

2.7 m

4 ft

1.2 m

12 ft

 

3.7 m

V1 + H1 = 40 ft (12.2 m) Maximum

H1 = 20 ft (6.1 m) Maximum

V1 = 6 inches (152 mm) Minimum

Two Elbows

H2H1

V1

V1 Minimum

H1 + H2 Maximum

1 ft

305 mm

Cannot do

 

 

 

 

1-1/2 ft

457 mm

1-1/2 ft

457 mm

 

 

 

 

2 ft

610 mm

3 ft

914 mm

3 ft

914 mm

6 ft

1.8 m

4 ft

1.2 m

9 ft

2.7 m

 

 

 

 

V1 + H1+ H2 = 50 ft (15.2 m) Maximum

H1 + H2 = 17 ft (5.2 m) Maximum V1 = 1-1/2 ft (457 mm) Minimum

Figure 5.4

INSTALLED

HORIZONTALLY

Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP2110-900 Rev. F • 6/08

13

Page 13
Image 13
Heat & Glo LifeStyle 6000GCF-IPI D. Vent Diagrams, Top Vent - Horizontal Termination One Elbow, Two Elbows, V1 H1