Heat & Glo LifeStyle 6000GCF-IPILP B. Wall Penetration Framing, Combustible Wall Penetration

Models: 6000GCF-IPI 6000GCF-IPILP

1 56
Download 56 pages 39.21 Kb
Page 18
Image 18
B. Wall Penetration Framing

B. Wall Penetration Framing

NOTE: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102

mm)the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.

 

 

 

 

3 IN. TOP

HEAT

 

 

CLEARANCE

SHIELD

 

 

HEAT

 

 

 

 

 

 

 

 

SHIELD

 

 

 

 

 

 

 

 

 

 

12 in.

10 in.

B

A

WALL WALL SHIELD

FIRESTOP

Combustible Wall Penetration 1 IN. CLEARANCE BOTTOM SIDES

A*

B

49-1/2 in.

48-1/2 in.

*Shows center of 10” x 12” vent framing hole for top venting. The center of the hole is (1) inch (25.4 mm) above the center of the horizontal vent pipe. With minimum vertical or 12 inch and 90º elbow.

Figure 6.6 Exterior Wall Hole

Figure 6.5 Horizontal venting clearances to combustible materials

Combustible Wall Penetration

Frame a hole in a combustible wall for an interior wall shield firestop, (Figure 6.3) whenever a wall is penetrated. Use same size framing materials as those used in the wall construction. The wall shield firestop maintains minimum clearances and prevents cold air infiltration.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus- tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.

If your local inspector requires the wall shield firestop on both sides, then both wall shield firestops must have a heat shield attached to them.

18

Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP2110-900 Rev. F • 6/08

Page 18
Image 18
Heat & Glo LifeStyle 6000GCF-IPILP owner manual B. Wall Penetration Framing, Combustible Wall Penetration