Heat & Glo • ESC-42ST • 2146-900 Rev. o • 5/12 21
D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-

ances as speci ed. Framing or nishing material closer than

the minimums listed must be constructed entirely of non-

combustible materials (i.e., steel studs, concrete board, etc).

Failure to comply could cause re.

Combustible Mantels

Non-combustible Mantels

Combustible Mantel Legs or Wall Projections

Non-Combustible Mantel Legs or Wall Projections

Figure 5.3 Clearances to mantels or other combustibles
above appliance
1 IN. MIN.
13 IN. MIN.
FROM OPENING
COMBUSTIBLE WALL OR
MANTEL LEG
FIREPLACE
OPENING
7 IN.
6 IN. MIN. FROM
OPENING
6 IN.
MAX.
COMBUSTIBLE
MATERIAL
Figure 5.5 Clearances to Combustible Mantel Legs or Wall
Projections.
1 IN. MIN.
13 IN. MIN.
4 IN. MAX.
FIREPLACE
OPENING
NON-COMBUSTIBLE WALL
NON-COMBUSTIBLE
MANTEL LEG
Figure 5.6 Clearances to Non-Combustible Mantel Legs or
Wall Projections.

10 IN.

MIN.

FIREPLACE

OPENING

12 IN.

MAX.

Figure 5.4 Clearances to Mantels or other Non-Combustibles
Above Appliance
FIREPLACE
OPENING
10 IN.
MIN.
4 IN.
MAX.
12 IN.
MAX.
NON-COMBUSTIBLE
MATERIAL