D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing or finishing material closer than the minimums listed must be constructed entirely of non- combustible materials (i.e., steel studs, concrete board, etc). Failure to comply could cause fire.

Combustible Mantels

12 IN.

MAX.

10 IN.

MIN.

FIREPLACE

OPENING

Figure 5.3 Clearances to mantels or other combustibles above appliance

Non-combustible Mantels

12 IN. MAX.

10 IN.

MIN.

4 IN.

MAX.

NON-COMBUSTIBLE MATERIAL

FIREPLACE

OPENING

Figure 5.4 Clearances to Mantels or other Non-Combustibles Above Appliance

Combustible Mantel Legs or Wall Projections

FIREPLACE

1 IN. MIN.

OPENING

 

 

COMBUSTIBLE

 

MATERIAL

 

6 IN.

 

MAX.

 

7 IN.

 

6 IN. MIN. FROM

 

OPENING

 

13 IN. MIN.

 

FROM OPENING

 

COMBUSTIBLE WALL OR

 

MANTEL LEG

Figure 5.5 Clearances to Combustible Mantel Legs or Wall Projections.

Non-Combustible Mantel Legs or Wall Projections

FIREPLACE

 

OPENING

1 IN. MIN.

4 IN. MAX.

NON-COMBUSTIBLE

 

MANTEL LEG

 

13 IN. MIN.

 

NON-COMBUSTIBLE WALL

Figure 5.6 Clearances to Non-Combustible Mantel Legs or Wall Projections.