1. Top Vent - Horizontal Termination

WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

1. Top Vent - Horizontal Termination

One Elbow

 

 

Note: Must have a 24 inches minimum

Note: Flue restrictor is permit-

 

vertical vent before attaching any

ted ONLY on 30 ft. minimum

 

elbow to the appliance.

vertical runs with no elbows.

 

 

 

 

 

V1

H1

V1 Minimum

H1

Maximum

2 ft

610 mm

7 in*

 

178 mm

 

 

 

 

 

3 ft

914 mm

2 ft

 

610 mm

4 ft

1.2 m

4 ft

 

1.2 m

5 ft

1.5 m

9 ft

 

2.7 m

 

 

 

 

 

6 ft

1.8 m

12 ft

 

3.7 m

 

 

 

 

 

7 ft

2.1 m

14 ft

 

4.3 m

10 ft

3.0 m

20 ft

 

6.1 m

20 ft

6.1 m

40 ft

 

12.2 m

 

 

 

 

 

After V1= 6 ft then H1 = 2 x V ft Maximum

V1 + H1 = 60 ft Maximum

*when used with approved termination caps

Figure 7.3

Two Elbows

Note: Flue restrictor is permit-

 

Note: Must have a 24 inches minimum

ted ONLY on 30 ft. minimum

 

vertical vent before attaching any

vertical runs with no elbows.

 

elbow to the appliance.

 

 

 

H2

V1

H1

 

V1 Minimum

H1+ H2

3 ft

914 mm

18 in

457 mm

 

 

 

 

4 ft

1.2 m

3 ft

914 mm

5 ft

1.5 m

7 ft

2.1 m

6 ft

1.8 m

10 ft

3.0 m

 

 

 

 

7 ft

2.1 m

12 ft

3.7 m

10 ft

3.0 m

18 ft

5.5 m

20 ft

6.1 m

20 ft

6.1 m

After V1= 6 ft then H1 = 2 x V1 ft Maximum

V1 + H1 + H2= 60 ft Maximum

H1 + H2= 20 ft Maximum

INSTALLED

HORIZONTALLY

Figure 7.4

Heat & Glo • ESC-42ST2146-900 Rev. o • 5/12

27

Page 27
Image 27