E. Hearth Extension

WARNING! Risk of Fire! Hearth extension required to protect combustible floors in front of appliance.

WARNING! Risk of Fire! DO NOT block ventilation slots. A minimum 1/4 in. space between the bottom of hearth refractory and top of field installed hearth exten- sion (marble, tile, granite, etc) is required across full width of fireplace.

If the appliance is to be placed directly on the floor, the non-combustible hearth material will be limited to 3/4 in. thick, including the floor adhesive. If the hearth mate- rial will exceed 3/4 in. thick, the appliance will need to be shimmed from the floor appropriately to maintain 1/4 in. minimum space between the floor hearth and hearth refractory.

The base of the fireplace may sit on a combustible surface. The area in front of the fireplace must be protected by a noncombustible hearth extension, unless the fireplace is raised a minimum of three inches above the combustible floor or hearth. See Figures 5.7, 5.8 and 5.10.

NON-COMBUSTIBLE

 

 

MATERIAL ON SIDES

 

 

(PROFILE VIEW)

 

 

MINIMUM

 

 

1/4 INCH SPACE

 

REQUIRED

 

MARBLE, GRANITE, TILE OR

 

 

OTHER NON-COMBUSTIBLE

 

 

HEARTH EXTENSION

 

 

3/4 IN. MAX

 

 

12 IN.

 

 

WOOD OR OTHER

HEARTH

BOTTOM OF

COMBUSTIBLE FLOOR

REFRACTORY

FIREPLACE

OR PLATFORM

 

 

Figure 5.7 Fireplace Positioned on Combustible Surface

MINIMUM

 

 

1/4 INCH SPACE

 

 

REQUIRED

 

 

3-3/4 IN.

BOTTOM OF FIREPLACE

3 IN.

 

MIN.

 

COMBUSTIBLE MATERIAL

 

WOOD OR OTHER

1 IN. MAX THICKNESS

 

ALLOWED UNDER

 

COMBUSTIBLE

 

FIREPLACE

 

FLOOR OR PLATFORM

 

 

 

Figure 5.8 Fireplace Raised A Minimum of 3 Inches Above Combustible Surface

23 IN.

 

3-1/2 IN.

 

NO COMBUSTIBLES

1/2 IN. BUILDING MATERIAL

IN THIS AREA

(MAY BE COMBUSTIBLE)

 

39 IN.

COMBUSTIBLE

 

 

FRAMING

4 IN.

 

 

FACTORY-

 

SUPPLIED 1/2 IN.

 

NON-

 

COMBUSTIBLE

 

BOARD

Figure 5.9 Non-Combustible Zone

 

 

A

 

A

B

 

B

in. 60-1/4 12

mm

1530

305

Figure 5.10 Non-Combustible Hearth Extension Minimum

Dimensions (Fireplace Positioned on Combustible

Surface)

22

Heat & Glo • ESC-42ST2146-900 Rev. o • 5/12