Specifications

Specifications

 

 

Indoor unit type

 

Ceilling Cassette - 4way

 

 

 

 

 

 

 

 

Model

 

DMC24CA-1

DMC36CA-1

 

 

 

 

 

 

Power supply

 

Phase/Volts/Hz

1 / 208-230 / 60

1 / 208-230 / 60

 

 

 

 

 

 

Cooling capacity

 

kW

7.03

9.96

 

 

 

 

 

 

 

 

 

Btu/h

24,000

34,000

 

 

 

 

 

 

Heating capacity

 

kW

-

-

 

 

 

 

 

 

 

 

 

Btu/h

-

-

 

 

 

 

 

 

Current

 

Nominal running current

A

1.0

1.0

 

 

 

 

 

 

Fan

 

Motor Type

 

BLDC

BLDC

 

 

 

 

 

 

 

 

Fan Type

 

Turbo Fan

Turbo Fan

 

 

 

 

 

 

 

 

Motor Output(W) * number of units

50.6 * 1

50.6 * 1

 

 

 

 

 

 

 

 

Air flow rate (H/M/L)

cmm

18.4/17.0/15.6

24.1/22.7/21.2

 

 

 

 

 

 

 

 

 

cfm

650/600/550

850/800/750

 

 

 

 

 

 

 

 

Capacitor

mF/V

-

-

 

 

 

 

 

 

 

 

Drive

 

DC

DC

 

 

 

 

 

 

Coil

 

Row * stages * FPI

mm

2R * 9C * 18

2R * 9C * 18

 

 

 

 

 

 

Dimensions

 

Body

mm(inch)

840 * 840 * 225(331/16 * 331/16 * 87/8)

840 * 840 * 225(331/16 * 331/16 * 87/8)

(W*D*H)

 

Decorative Panel

mm(inch)

950 * 950 * 30(3713/32 * 3713/32 * 13/16)

950 * 950 * 30(3713/32 * 3713/32 * 13/16)

Net Weight

 

Body

kg(lbs)

26(57.3)

26(57.3)

 

 

 

 

 

 

 

 

Decorative Panel

kg(lbs)

3(6.61)

3(6.61)

 

 

 

 

 

 

Gross Weight

 

Body

kg(lbs)

30(66)

30(66)

 

 

 

 

 

 

 

 

Decorative Panel

kg(lbs)

4(9)

4(9)

 

 

 

 

 

 

Air filter

 

 

Long Life filter

Long Life filter

 

 

 

 

 

 

Sound Level (H/M/L)

 

dB(A)+3

38/35/32

40/37/34

 

 

 

 

 

 

Piping Connections

 

Liquid

mm(inch)

6.35(1/4)

6.35(1/4)

 

 

 

 

 

 

 

 

Gas

mm(inch)

12.7(1/2)

15.88(5/8)

 

 

 

 

 

 

Drain

 

OD/ID

mm(inch)

32/25(1.26/0.98)

32/25(1.26/0.98)

 

 

 

 

 

 

Dehumidification rate

 

l/h(pts/h)

3.0(6.3)

3.7(7.8)

 

 

 

 

 

 

Safety Devices

 

 

Fuse, Thermal protector for Fan motor

 

 

 

 

 

 

Temperature sensor

 

 

Thermistor

Thermistor

 

 

 

 

 

 

Refrigerant

 

 

R410A

R410A

 

 

 

 

 

 

Refrigerant control

 

 

EEV

EEV

 

 

 

 

 

Connectable outdoor Unit

 

Single

Single

 

 

 

 

 

Power and Transmission interunit cable

No.* mm2 (No. AWG)

4 * 2.1(14)

4 * 2.1(14)

 

 

 

 

 

 

Note :

1.Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7°C(80°F) DB /19.4°C(67°F) WB

-Outdoor Temperature 35°C(95°F) DB /23.9°C(75°F) WB Piping Length - Interconnecting Piping Length 7.5m(25ft)

-Level Difference of Zero.

Conversion Formula

kW = Btu/h 0.0002931

CFM = CMM 35.3

Service Manual 13

Page 13
Image 13
Heat Controller DMC36CA-1, DMC24CA-1 manual Specifications