Troubleshooting Guide

Troubleshooting CH41, CH44,CH45,CH46,CH47, CH65

Display

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

41

 

• Open / Short

• Normal resistor : 200K/ at 25°C(77°F) (Unplugged)

D-pipe sensor (Inverter)

• Soldered poorly

• Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

• Normal resistor : 10K/ at 25°C(77°F) (Unplugged)

44

Air sensor

• Soldered poorly

• Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

• Normal resistor : 5K/ at 25°C(77°F) (Unplugged)

45

Condenser Pipe sensor

• Soldered poorly

• Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

• Normal resistor : 5K/ at 25°C(77°F) (Unplugged)

46

Suction Pipe sensor

• Soldered poorly

• Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

• Normal resistor : 200K/ at 25°C(77°F) (Unplugged)

47

D-pipe sensor (Constant)

• Soldered poorly

• Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

• Open / Short

• Normal resistor : 10K/ at 25°C(77°F) (Unplugged)

65

Heat sink sensor

• Soldered poorly

 

 

• Internal circuit error

• Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

 

 

Check Point

1.

Estimate the resistance of each sensor.(Unplugged)

2.

Estimate the voltage of each sensor.(Plugged)

3.

If the resistance of the sensor is 0 kor ,

then sensor is abnormal.

If the voltage of the sensor is 0 V or 5Vdc,

then sensor is abnormal.

44Ceiling Cassette Air Conditioner

Page 44
Image 44
Heat Controller DMC24CA-1, DMC36CA-1 manual Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65