Heat Controller DMC36CA-1, DMC24CA-1 Heat Insulation and pipings, Installation, Form The Pipings

Models: DMC36CA-1 DMC24CA-1

1 52
Download 52 pages 2.95 Kb
Page 25
Image 25
6. Heat Insulation and pipings

Installation

6. Heat Insulation and pipings

HEAT INSULATION

1.Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C(248°F) ).

2. Precautions in high humidity circumstance:

This air conditioner has been tested according to

the "KS Standard Conditions with Mist" and con here is not any default. However, if it is operated for a long time in high humid atmosphere (dew point

temperature: more than 23°C(73.4°F)), water drops Indoor unit are liable to fall. In this case, add heat insulation

material according to the following procedure:

Fastening band (accessory)

Refrigerant piping

Thermal insulator (accessory)

Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm(0.39 to 0.79inch).

Stick glass wool on all air conditioners that are located in ceiling atmosphere.

In addition to the normal heat insulation (thickness: more than 8mm(0.31inch)) for refrigerant piping (gas

piping: thick piping) and drain piping, add further 10mm to 30mm(0.39inch to 1.18 inch) thickness material.

FORM THE PIPINGS

1.Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings)

If you want to connect an additional drain hose, the end of the drain-outlet should be kept at a distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)

In case of the Outdoor unit being installed below position of the Indoor unit.

2.Tape the Piping, drain hose and Connecting Cable from bottom to top.

3.Form the piping gathered by taping along the exterior wall and attach it to the wall by saddle or

equivalent.

Seal a small opening around the pipings with gum type sealer.

Plastic Band

Drain hose Taping

Pipings

Connecting cable

Power supply cord

HEAT INSULATION Trap is required to prevent water from entering into electrical parts.

Service Manual 25

Page 25
Image 25
Heat Controller DMC36CA-1, DMC24CA-1 manual Heat Insulation and pipings, Installation, Form The Pipings