Trouble 5 When Vertical Louver does not operate

Troubleshooting Guide

Trouble 5 When Vertical Louver does not operate

Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.

If the regular torque is detected when rotating the Vertical Louver with hands 36Ceiling Cassette Air Conditioner Normal

Check the connecting condition of CN-U/D Connector

Check the soldering condition(on PWB) of CN-U/D Connector

Check the operating circuit of the Vertical Louver

Confirm that there is DC +12V between pin Manual background(RED) of CN-U/D and GND.

If there are no problems after above checks

Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver