Heat Controller DMC36CA-1, DMC24CA-1 TroubleshootingCH32,CH33, Check Point, Troubleshooting Guide

Models: DMC36CA-1 DMC24CA-1

1 52
Download 52 pages 2.95 Kb
Page 43
Image 43
TroubleshootingCH32,CH33

Troubleshooting Guide

Manual backgroundManual backgroundTroubleshootingManual backgroundCH32,Manual backgroundCH33Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Display

Title

 

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

D-pipe (Inverter)

 

• Check the discharge pipe sensor for INV.

 

• Discharge sensor

• Check the install condition for over load.

32

temp. high

 

 

(105°C(221°F)

)

(Inverter) temp. high

• Check the leakage of refrigerant.

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

D-pipe (Constant)

 

• Check the discharge pipe sensor for Cons.

 

• Discharge sensor

• Check the install condition for over load.

33

temp. high

 

 

(Cons.) temp. high

• Check the leakage of refrigerant.

 

(105°C(221°F)

)

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

105° C

COMP OFF

 

(221° F)

 

 

 

95° C

LEV OPEN/Hz down

 

(203° F)

LEV OPEN/Hz down

 

90° C

 

 

 

(194° F)

NORMAL

 

 

 

 

 

 

 

Inverter

Check Point

• CH 32

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

105° C

COMP OFF

(221° F)

 

90° C

LEV OPEN

(194° F)

LEV OPEN

80° C

 

(176° F)

NORMAL

 

 

Constant

• CH 33

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

4.Check the constant compressor. (same with CH21)

Service Manual 43

Page 43
Image 43
Heat Controller DMC36CA-1, DMC24CA-1 manual TroubleshootingCH32,CH33, Check Point, Troubleshooting Guide