Troubleshooting Guide

TroubleshootingCH04

Display

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

• The connection of wire(Drain pump/ Float switch)

04

Drain pump

• Float switch Open.

• Drain pump power input. (220V)

/ Float switch

(Normal : short)

• Drain tube installation.

 

 

 

 

• Indoor unit installation. (Inclination)

 

 

 

 

CN Float

0

Check the resistance

Check Point

1.Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.

2.Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.

3.Check the level of water

4.Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

40Ceiling Cassette Air Conditioner

Page 40
Image 40
Heat Controller DMC24CA-1, DMC36CA-1 manual Troubleshooting CH04, Drain pump Float switch Open Drain pump power input