Operation

SDC / DHC

 

 

5.4.13"Cascading" menu (CASCADE)

The parameters in this menu refer solely to the parameters that are associated with the cascading of multiple heat generators.

This selection is only available if multiple heat generators exist in the control system.

Para-

Designation

Setting range / Setting values

Factory

Setting

meter

 

 

setting

 

01

Switching

0.5... 30 K

8

 

 

differential

 

 

 

 

 

 

 

 

02

Connection delay

0 ... 200 min

0

 

 

 

 

 

 

03

Switch-off delay

0 ... 60 min

0

 

 

 

 

 

 

04

Switchover power

10 ... 100 %

65

 

 

of stage sequence

 

 

 

 

 

 

 

 

05

Stage reversal

OFF, 1 to 250 h

OFF

 

 

 

 

 

 

06

Guidance stage

1 ... maximum number of stages

1

 

 

 

 

 

 

07

Peak-load stage

OFF, 2 ... maximum number of

OFF

 

 

 

stages

 

 

 

 

All heat generators are numbered

 

 

 

 

consecutively within the cascade.

 

 

 

 

The total quantity determines the

 

 

 

 

maximum number of stages.

 

 

 

 

 

 

 

08

Switchover of base

OFF, ON

OFF

 

 

load with grouping

 

 

 

 

 

 

 

 

09

Quick hot-water

OFF, 1 ... maximum number of

OFF

 

 

connection

stages

 

 

 

 

 

 

 