Honeywell EN2H-0221GE51 R0808 service manual Timeprograms menu Access Returning

Models: EN2H-0221GE51 R0808

1 258
Download 258 pages 27.36 Kb
Page 55
Image 55

SDC / DHC

Operation

 

 

5.2.2"Timeprograms" menu

NOTE

Access

Returning

Individualised switching time programs for heating and hot-water operation can be created in this menu. Here, the factory-set default programs P1 (and, if enabled, P2 and P3 as well) of each heating circuit and the hot-water circuit are overwritten by individualised switching times and temperature specifications. This is especially advantageous if correspondingly adapted heating programs are to be created in case of periodically recurring assignments with different assignment times (e.g. shift work). Max. three heating cycles, each with a switch-on and switch-off time, are available for each day of the week for programming switching times. Each heating cycle can also be combined with a freely-selectable temperature specification.

The default programs are not lost when overwritten by individually created programs. Individualised programs, however, are deleted when default programs are reloaded and must be recreated. For this reason, individualised switch-on / switch-off times and temperature specifications should always be entered in the tables provided for this purpose (see 9 Log, pg. 254).

Press button.

Returning to the basic display takes place by pressing the button or automatically after the set information time (see 5.1.2.7 "System information" button, pg. 35).

EN2H-0221GE51 R0808

55

Page 55
Image 55
Honeywell EN2H-0221GE51 R0808 service manual Timeprograms menu Access Returning