SDC / DHC

 

 

 

 

 

 

 

Control Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

Adjustable

 

Inputs

 

 

 

Comment

 

 

at output

 

Fixed

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

assign

 

(VI 1/2)

 

 

 

 

 

 

ment

 

 

 

 

Buffer loading pump

 

VA1, VA2

PF

 

PF1 (19)

Fixed assignment to VI if PLP is

(SDC 8-21, SDC 9-21,

 

 

 

 

 

 

 

set to PF. Otherwise, PF1 can

SDC 12-31,

 

 

 

 

 

 

 

be adjusted at free VI (activation

DHC 43-2)

 

 

 

 

 

 

 

of buffer management)

 

 

 

 

 

 

 

Solid-fuel loading

 

VA1, VA2

FKF

 

FPF (18)

SFS in fixed assignment to

pump

 

 

 

 

 

 

 

corresponding VI; standard

 

 

 

 

 

 

 

 

buffer sensor is KSPF; separate

 

 

 

 

 

 

 

 

solid-fuel buffer tank sensor SFB

 

 

 

 

 

 

 

 

can be configured (optional)

 

 

 

 

 

 

 

Stratified tank loading

 

VA1, VA2

SSLP

---

 

 

pump (DHC 43-2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solar loading valve

 

VA1, VA2

SLVF

----

 

SLVS in DHW storage; KSPF in

 

 

 

 

 

 

 

 

buffer

 

 

 

 

 

 

 

 

Solar forced

 

VA1, VA2

 

 

 

 

 

dissipation valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.2Switching time program enabling

The modular Smile SDC/DHC 43 series of controllers features three switching time programs for each heating circuit that can be set separately.

When supplied, only one switching time program is enabled. The use of only a single switching time program for a wide range of applications makes it possible to simplify operation.

See also 5.2.3.2 Time program, Pg. 73