Operation

SDC / DHC

 

 

5.4.11"Buffer" menu (BUFFER)

The parameters in this menu refer to special settings with regard to solids regulation.

Enabling occurs only with corresponding activation in the "Hydraulics" menu.

Para-

Designation

Setting range / Setting values

Factory

Setting

meter

 

 

 

setting

 

01

Minimum

5 °C to setting value of parameter

20

 

 

temperature

02

 

 

 

 

 

 

 

 

 

02

Maximum

Setting value of parameter

80

 

 

temperature

01 to 95 °C

 

 

 

 

 

 

 

 

 

03

Boiler temperature

–10 to 80 K

 

0

 

 

increase

 

 

 

 

 

 

 

 

 

 

04

Buffer switching

1 to 70 K

 

2

 

 

differential

 

 

 

 

 

 

 

 

 

 

05

Forced discharge

OFF

 

OFF

 

 

 

1

In process water tank

 

 

 

 

2

In heating circuits

 

 

 

 

 

 

 

 

06

Follow-up switch-

OFF, (setting value of parameter

10

 

 

on differential

07 + 2 K) to 50 K

 

 

 

 

 

 

 

 

07

Follow-up switch-

1 K to (setting value of parameter

5

 

 

off differential

06 – 2 K)

 

 

 

 

 

 

 

 

 

08

Buffer start-up

OFF

No start-up

ON

 

 

protection

 

protection

 

 

 

 

ON

Start-up protection

 

 

 

 

 

active

 

 

 

 

 

 

 

 

09

Buffer discharge

OFF

No discharge

ON

 

 

protection

 

protection

 

 

 

 

ON

Discharge protection

 

 

 

 

 

active

 

 

 

 

 

 

 

 

108

EN2H-0221GE51 R0808

Page 108