5.2.3.3.2Individualised night-time room temperature for each heating circuit

Setting ► Press ¦ button.

C

Select desired heating circuit (HC, MC-1 or MC-2) by turning the input button î.

Confirm selected circuit by pressing the input button î.

Set flashing room temperature specification to the desired value by turning the input button î.

Confirm set value by pressing the ¦ button.

Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).

Setting range

5 ... 30 °C

Factory setting

16 °C

5.2.3.3.3Individualised operating mode for each heating circuit

Each heating circuit can be assigned an individualised operating mode.

Setting

C

Press button.

Select desired heating circuit (HC, MC-1 or MC-2) by turning the input button î.

Confirm selected circuit by pressing the input button î.

Select flashing operating mode by turning the input button î.

Confirm set operating mode by pressing the button or the input button î.

With short-term operating modes (ABSENT, PARTY), set desired target value by turning the input button î and confirm set value by pressing the input button î.

Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).

This parameter specifies the end of heating operation depending on the outside temperature based on the following criteria: