Para-

 

Designation

Setting range / Setting values

Factory

Setting

meter

 

 

 

setting

 

10

 

Reset heat

SET by pressing the input button

 

 

 

balance

 

 

 

 

 

 

 

 

 

11

 

Volume flow

0 ... 30 L/min or L/pulse

0

 

 

 

 

 

 

 

12

 

Density of medium

0.8 ... 1.2 kg/L

1.05

 

 

 

 

 

 

 

13

 

Heat capacity of

2 ... 5 KJ/kgK

3.6

 

 

 

medium

 

 

 

 

 

 

 

 

 

14

 

Final switch-off

OFF, 90 to 210 °C

210

 

 

 

temperature

 

 

 

 

 

 

 

 

 

15

 

Test cycle of solar

1 ... 60 min

10

 

 

 

charging

 

 

 

 

 

switchover

 

 

 

 

 

 

 

 

 

16

 

Switchover tem-

20 ... 110 °C

75

 

 

 

perature

 

 

 

 

 

 

 

 

 

5.4.10"Solid" menu (SOLID FUEL)

The parameters in this menu refer to special settings with regard to solids regulation.

Enabling occurs only with corresponding activation in the "Hydraulics" menu.

Para-

Designation

Setting range / Setting values

Factory

Setting

meter

 

 

 

setting

 

01

Minimum

20

... 80 °C

60

 

 

temperature

 

 

 

 

 

 

 

 

 

 

02

Maximum

30

... 100 °C

90

 

 

temperature

 

 

 

 

 

 

 

 

 

03

Switch-on

(Setting value of parameter

10

 

 

differential

04

+ 3 K) to 20 K

 

 

 

 

 

 

 

04

Switch-off

2 K to (setting value of parameter

5

 

 

differential

03

– 3 K)

 

 

 

 

 

 

 

05

Heat generator

OFF, 2 to 180 min

OFF

 

 

cycle inhibitor

 

 

 

 

 

 

 

 

 

 