PDX SERVICE PROCEDURE V
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Testing.
Step 1. Position power switch on gas control to the “OFF” position.
WARNING
120 volt potential exposure. Use caution
to avoid personal injury.
15
Step 2. Remove tubing from inlet pressure tap.
Step 3. Remove the three screws (Phillips screw driver) from control access cover on blower and remove cover (see photo 15).
Step 4. Locate blower temperature switch (see photo 16)
Switch Setting
Opens on rise @ approximately 155°F
Auto resets on fall @ approximately 128°F
Cool switch to
below 125°F
Disconnect wire leads to | N |
|
|
| ||||
switch. Using a | Replace switch | |||||||
set to the ohms setting, is |
|
| ||||||
|
| (see page 24) | ||||||
there continuity between the |
| |||||||
|
|
|
| |||||
switch terminals? |
|
|
|
| ||||
| Y |
|
|
|
| |||
|
|
|
|
| ||||
|
|
|
|
|
| N | ||
Reconnect wire leads and |
|
| ||||||
Y | Do switch contacts Y | |||||||
observe heater operation. Do | ||||||||
exhaust gas temperatures rise |
|
| open? |
| ||||
to or above 175°F? |
|
|
|
| ||||
| N |
|
|
|
| |||
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
Do switch contacts Y |
| Replace switch | ||||||
open? |
|
|
| (see page 23) |
16
Blower temperature
switch location
Air mixing inlet
|
|
|
| Common causes for |
| |
|
|
| high exhaust temperature |
| ||
Exhaust |
| 1. Vent length is below minimum allowable. | ||||
temperature is too |
| 2. Vent diameter not to specification. | ||||
| ||||||
hot. |
| 3. Restricted dilution air inlet. | ||||
|
| 4. Missing or deteriorated flue baffle. | ||||
|
| 5. Gas pressure is out of specification. | ||||
|
| 6. Excessively high ambient temperatures. |
N
Switch OK
Page 22
22