Honeywell PDX150S*F(BN,SX,CX), PDX75S70F(B,S,C)*(N,X) PDX Series, Vent Tables, Specifications

Models: PDX140S*F(BN,SX,CX) PDX440S*F(BN,SX) PDX75S70F(B,S,C)*(N,X) PDX275T*F(BN,SX,CX) PDX150S*F(BN,SX,CX) PDX65S65F(B,S,C)*(N,X) PDX265T*F(BN,SX,CX) PDX50S60F(B,S,C)*(N,X) PDX450S*F(BN,SX) PDX250T*F(BN,SX,CX)

1 40
Download 40 pages 45.12 Kb
Page 7
Image 7
Vent Tables

PDX Series

Specifications

Venting Specifications for:

Vent Tables

 

 

 

 

48Gallon

65Gallon

75Gallon

This water heater is approved for installation with the following PVC, CPVC or ABS Schedule 40 venting material.

The maximum and minimum vent lengths listed on this label are for the exhaust portion of the vent. The intake portion of the vent must be equal to or less than the length of the exhaust.

3" Diameter (7.6 cm) PVC Vent Connector Lengths

 

# of

Maximum 48, 65 gal.

Maximum 75 gal.

Terminating

 

 

 

 

 

 

Maximum

Minimum

Maximum

Minimum

Elbows

 

Length ft (m)

Length ft (m)

Length ft (m)

Length ft (m)

 

 

 

 

 

 

 

 

Through the Wall

1

55 (16.8)

2 (.6)

45 (13.7)

2 (.6)

 

 

 

 

 

 

 

 

Through the Wall

2

50 (15.2)

2

(.6)

40 (12.2)

2

(.6)

Through the Wall

3

45 (13.7)

2

(.6)

35 (10.7)

2

(.6)

 

 

 

 

 

 

 

 

Through the Wall

4

40 (12.2)

2

(.6)

30 (9.1)

2

(.6)

 

 

 

 

 

 

 

 

 

 

 

 

Through the Roof

0

60 (18.3)

7 (2.1)

50 (15.2)

7 (2.1)

 

 

 

 

 

 

Through the Roof

1

55 (16.8)

7 (2.1)

45 (13.7)

7 (2.1)

Through the Roof

2

50 (15.2)

7 (2.1)

40 (12.2)

7 (2.1)

 

 

 

 

 

 

Through the Roof

3

45 (13.7)

7 (2.1)

35 (10.7)

7 (2.1)

 

 

 

 

 

 

 

 

 

4" Diameter (10.2 cm) PVC Vent Connector Lengths

 

 

 

 

 

 

 

 

# of

Maximum 48, 65 gal.

Maximum 75 gal.

Terminating

 

 

 

 

 

 

Maximum

Minimum

Maximum

Minimum

Elbows

 

Length ft (m)

Length ft (m)

Length ft (m)

Length ft (m)

 

 

 

 

 

 

 

 

Through the Wall

1

95 (29.0)

10 (3.1)

85 (25.9)

10 (3.1)

 

 

 

 

 

 

 

 

Through the Wall

2

90 (27.4)

10

(3.1)

80 (24.4)

10

(3.1)

 

 

 

 

 

 

 

 

Through the Wall

3

85 (25.9)

10

(3.1)

75 (22.9)

10

(3.1)

Through the Wall

4

80 (24.4)

10

(3.1)

70 (21.3)

10

(3.1)

 

 

 

 

 

 

Through the Wall

5

75 (22.9)

12 (3.6)

65 (19.8)

12 (3.6)

 

 

 

 

 

 

 

 

Through the Roof

0

100 (30.5)

15 (4.6)

90 (27.4)

15 (4.6)

 

 

 

 

 

 

 

 

Through the Roof

1

95 (29.0)

15

(4.6)

85 (25.9)

15

(4.6)

 

 

 

 

 

 

 

 

Through the Roof

2

90 (27.4)

15

(4.6)

80 (24.4)

15

(4.6)

 

 

 

 

 

 

 

 

Through the Roof

3

85 (25.9)

15

(4.6)

75 (22.9)

15

(4.6)

Through the Roof

4

80 (24.4)

15

(4.6)

70 (21.3)

15

(4.6)

 

 

 

 

 

 

 

 

Page 7

7

Page 7
Image 7
Honeywell PDX150S*F(BN,SX,CX), PDX75S70F(B,S,C)*(N,X), PDX65S65F(B,S,C)*(N,X) PDX Series, Vent Tables, Specifications