Honeywell PDX50S60F(B,S,C)*(N,X) Control Timings, PDX Series, Specifications, Ignition State

Models: PDX140S*F(BN,SX,CX) PDX440S*F(BN,SX) PDX75S70F(B,S,C)*(N,X) PDX275T*F(BN,SX,CX) PDX150S*F(BN,SX,CX) PDX65S65F(B,S,C)*(N,X) PDX265T*F(BN,SX,CX) PDX50S60F(B,S,C)*(N,X) PDX450S*F(BN,SX) PDX250T*F(BN,SX,CX)

1 40
Download 40 pages 45.12 Kb
Page 9
Image 9
Control Timings

PDX Series

Specifications

Control Timings

Ignition State

 

Timing

 

 

 

 

 

 

Pre-purge

15 Seconds

 

 

Trial for Ignition

90 Seconds

 

 

Flame Stabilization Period

3 Seconds

 

 

Inter-purge

15 Seconds

 

 

Flame Failure Response Time

1.5 Seconds (2 second. Maximum; 1 second minimum.)

 

 

Post-purge

15 Seconds

 

 

PS Fault Delay (failed open/close)

Retry after 2 Minutes

 

 

Soft Lockout

Retry after 5 Minutes

 

 

TCO Limit Lockout

Indefinite (cycle power to restart)

 

 

Verify Resistive Delay

Retry after 2 Minutes (repeats 5 times)

 

 

Simulated Resistive Load Lockout

Indefinite (cycle power to restart)

 

 

Hardware Error Lockout

Indefinite (self clears if fault clears for at least 15 seconds)

 

 

 

 

 

 

Page 9

9

Page 9
Image 9
Honeywell PDX50S60F(B,S,C)*(N,X), PDX75S70F(B,S,C)*(N,X) Control Timings, PDX Series, Specifications, Ignition State