b) Service Menu Chart

Service

 

Setting Range

 

Factory Default

Menu

Item and Details

Cabinet

 

Rail

Cabinet

 

Rail

F0

Defrost Interval

1 to 12 hours in

 

N/A

6

 

N/A

 

• The cabinet uses a time initiated

1 hour increments.

 

 

 

 

 

 

 

 

 

 

 

 

 

heated defrost.

 

 

 

 

 

 

 

• The change in the defrost

 

 

 

 

 

 

 

interval setting will take effect

 

 

 

 

 

 

 

immediately. The next defrost

 

 

 

 

 

 

 

will take place after the newly

 

 

 

 

 

 

 

set time interval has elapsed.

 

 

 

 

 

 

 

• Initiating a manual defrost on the

 

 

 

 

 

 

 

cabinet will restart the defrost

 

 

 

 

 

 

 

timer.

 

 

 

 

 

 

F1

Defrost Termination Temperature

41 to 68°F

 

N/A

49°F (9.4°C)

 

N/A

 

Do not adjust. For

(5 to 20°C)

 

 

 

 

 

 

recommendations, contact

in 1 degree

 

 

 

 

 

 

Hoshizaki Technical Support.

increments

 

 

 

 

 

F2

Setpoint Temperature Differential

Both the + and - values can be

Comp on

 

Comp on

 

Use "SET" button to scroll through

adjusted between 0 to 6.3°F in

0°F (0°C)

 

0°F (0°C)

 

all 4 settings.

increments of .9°F

 

at setpoint

 

at setpoint

 

• You cannot set both + and - to

(0 to 3.5°C in increments of .5°C)

 

 

 

 

(decimal not displayed)

 

Comp off

 

Comp off

 

0.0.

 

 

 

 

 

 

-3.6°F (-2°C)

-3.6°F (-2°C)

 

• Negative value indicated by LED

 

 

 

 

 

 

 

below setpoint

 

below setpoint

 

to left of number.

 

 

 

 

 

 

F3

High Temperature Alarm Delay

0 to 3 hours in 1 hour increments

 

2

 

Time: See "III.A. Alarm Signals."

 

 

 

 

 

 

F4

Low Temperature Alarm Delay

0 or 1 hour

 

 

1

 

Time: See "III.A. Alarm Signals."

 

 

 

 

 

 

F5

Temperature Display

Fahrenheit or Celsius

 

°F

F6

Alarm History: maximum 8 alarms.

Alarms displayed newest to oldest.

N/A

 

 

When "--" appears, you have

 

 

 

 

No reset for alarm history

reached the end of the alarm

 

 

 

 

available.

history.

 

 

 

 

F7

Compressor Run Time (%):

N/A

 

N/A

 

Displays compressor run time

 

 

 

 

 

 

 

percentage between the 2 most

 

 

 

 

 

 

 

recent defrosts.

 

 

 

 

 

 

F8

Not Used

N/A

 

N/A

F9

Rail Cooling Switch:

0=rail fans on continuously (same

N/A

 

2

 

"LOW" Rail Fan Adjustment (rail

as "NORMAL" position)

 

 

 

 

 

section only)

1=rail fans on 15 sec.

 

 

 

 

 

 

rail fans off 90 sec.

 

 

 

 

 

 

2=rail fans on 1 sec.

 

 

 

 

 

 

rail fans off 90 sec.

 

 

 

 

FA

High Condenser Temperature

Adjustable between 140 to 167°F

140°F (60°C)

Do not

Alarm Setting (clogged filter):

(60 to 75°C).

 

(1 not displayed)

adjust

For recommendations, contact

 

 

 

 

 

 

 

Hoshizaki Technical Support.

 

 

 

 

 

 

Fb

Audible Control

N/A

 

N/A

22

Page 22
Image 22
Hoshizaki 73168 service manual Service Menu Chart