4. Cabinet Defrost
| Problem | Possible Cause | 
 | 
 | Remedy | ||
| [1] | Cabinet fan motors | a) Cabinet Fan Relay | 1. | Bad contacts (closed). | 1. | Check for continuity and | 
| 
 | on. | 
 | 
 | 
 | 
 | replace. | 
| 
 | 
 | b) Control Board | 1. | Defective. | 1. | Replace. | 
| [2] | Evaporator does | a) Defrost Thermistor | 1. | Defective. | 1. | See "II.E. Thermistor | 
| 
 | not defrost | 
 | 
 | 
 | 
 | Check." | 
| 
 | completely. | b) Defrost | 1. | Not enough defrosts | 1. | Factory default is once | 
| 
 | 
 | 
 | 
 | occurring per day. | 
 | every 6 hours. See "II.D.5. | 
| 
 | 
 | 
 | 
 | Operation in humid | 
 | Service Menu." | 
| 
 | 
 | 
 | 
 | conditions. | 
 | 
 | 
| 
 | 
 | c) Defrost Heater | 1. | Defective. | 1. | Replace heater. | 
| 
 | 
 | d) Defrost Thermostat | 1. | Defective, turning off | 1. | Replace defrost thermostat. | 
| 
 | 
 | 
 | 
 | heaters prematurely, | 
 | 
 | 
| 
 | 
 | 
 | 
 | or fused open. | 
 | 
 | 
| 
 | 
 | e) Cabinet Liquid Line | 1. | Does not close. | 1. | Check and replace. | 
| 
 | 
 | Valve | 
 | 
 | 
 | 
 | 
| [3] | Defrost cycle too | a) Defrost | 1. | Not enough defrosts | 1. | Factory default is once | 
| 
 | long. (E3 Defrost | 
 | 
 | occurring per day. | 
 | every 6 hours. See "II.D.5 | 
| 
 | Alarm) | 
 | 
 | Operation in humid | 
 | Service Menu." | 
| 
 | 
 | 
 | 
 | conditions. | 
 | 
 | 
| 
 | 
 | b) Defrost Thermistor | 1. | Defective. | 1. | Replace. | 
| 
 | 
 | c) Defrost Heater | 1. | Defective. | 1. | Replace heater. | 
| 
 | 
 | d) Defrost Thermostat | 1. | Defective, turning off | 1. | Replace defrost thermostat. | 
| 
 | 
 | 
 | 
 | heaters prematurely, | 
 | 
 | 
| 
 | 
 | 
 | 
 | or fused open. | 
 | 
 | 
| 
 | 
 | e) Control Board | 1. | Defective. | 1. | Replace. | 