1. High Temperature Alarm (E1)

If the cabinet or rail temperature exceeds the setpoint temperature by 18°F (10°C) or more for more than x hours, "E1" is displayed. The default value of x is "2" (2 hours). The value of x can be changed under "F3" on the service menu. (0=No delay; 1=1; 2=2; 3=3 hours)

Note:

After the machine has been turned off and then turned back on, the high temperature alarm feature is not active until the area temperature reaches the lower setpoint temperature differential.

The high temperature alarm feature operates even during defrost.

Reset Options

The alarm will automatically reset once the area temperature reaches the lower setpoint temperature differential.

Possible Causes (for further details, see "III.B. Service Chart")

Doors or drawers are opened frequently or are not completely closed.

Trouble with the compressor or a refrigerant leak.

Trouble with the cabinet or rail thermistor.

Liquid line valve closed.

Power On

E1 Alarm Timer Reset

E1 Alarm not Available until

E1 Alarm

E1 Alarm Timer

Lower Setpoint is Achieved

over 2 hours

 

Timer under

 

 

2 hours

E1 Alarm

 

 

E1 Alarm Temperature 18°F

 

 

(10°C) above setpoint temp.

 

 

Setpoint Temperature and

 

 

Upper Setpoint Differential 0°F (0°C)

 

 

 

E1 Alarm

 

Lower Setpoint

Available

 

 

E1

Temperature Differential

Alarm

3.6°F (2°C)

 

 

Reset

 

 

 

Temperature Display

E1

 

 

 

 

Blinking

27

Page 27
Image 27
Hoshizaki 73168 service manual High Temperature Alarm E1, Reset Options