11.2 Extended storage

During extended storage in environments where the ambient temperature is –15 to +30 °C (+5 to +86 °F), charge the UPS’s battery every 6 months

During extended storage in environments where the ambient temperature is +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every 3 months.

12. Specifications

 

420 VA

650 VA

 

1000 VA

1400 VA

 

 

 

 

 

Acceptable input voltage

 

0 - 160 VAC

 

 

 

 

 

 

Input voltage (on-line operation)

 

92-150

VAC

 

 

 

 

 

 

Output voltage

 

103-132

VAC

 

 

 

 

 

Nominal input frequency

 

50 or 60 Hz, autosensing

 

 

 

 

 

Input Protection

 

Resettable circuit breaker

 

 

 

 

 

Frequency limits (on-line operation)

 

50 or 60 Hz, ±5%

 

 

 

 

 

Transfer time

 

2 ms typical, 4 ms maximum

 

 

 

 

 

 

Maximum load

420 VA 280 W

650 VA 400 W

 

1000 VA 670 W

1400 VA 950 W

 

 

 

 

 

On-battery output voltage

 

115 VAC

 

 

 

On-battery frequency

50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout.

 

 

 

On-battery waveshape

Stepped sine-wave

 

Trapezoid

 

 

 

Protection

Overcurrent and short-circuit protected, latching shutdown on overload.

 

 

 

 

 

 

Surge energy rating (one time,

320 J

 

480 J

10/1000 µs waveform)

 

 

 

 

 

 

 

 

 

 

 

 

Surge current capability (one time,

 

6500 A maximum

 

8/20 µs waveform)

 

 

 

 

 

 

 

 

 

 

 

Surge response time

 

0 ns (instantaneous) normal mode;

 

 

<5 ns common mode

 

 

 

 

 

 

 

 

 

 

Surge voltage let-through (percentage

0.7%

 

0.3%

of applied ANSI C62.41 Cat. A ±6

 

kV test waveform)

 

 

 

 

 

 

 

 

Noise Filter

Normal and common mode EMI/RFI suppression,

 

100 kHz to 10 MHz

 

 

 

 

 

 

Battery type

Spill proof, maintenance free, user replaceable, sealed lead-acid

 

 

Typical battery life

3 to 6 years, depending on number of discharge cycles and ambient

 

temperature

 

 

 

 

 

 

 

 

Typical recharge time

 

2 to 5 hours from total discharge

 

 

 

 

 

 

 

English

15