Component to be inspected | Task | Frequency | Capable Party | |
|
|
|
| |
EPO System Test | EPO | Annually | Qualified personnel | |
| Mode Key Switch Test - rotate |
|
| |
| keyed switch through all modes. |
|
| |
| ARMED MODE - Verify: |
|
| |
| • Power Indicator - White |
|
| |
| • Armed Light - White |
|
| |
| BYPASS MODE - Verify |
|
| |
| • Bypass Light - Green |
|
| |
| TEST MODE - Verify: |
|
| |
| • Test Light - Amber |
|
| |
| Press EPO button (each in |
|
| |
| succession) and thermal trip to |
|
| |
| verify: |
|
| |
| • Reset Light - White |
|
| |
| • | Audible alarm |
|
|
| • | Visual lamp indicator |
|
|
| Replace light upon failure |
|
| |
Emergency Lighting | Verify emergency lighting is | Every 2 years | Qualified personnel | |
| visible when all lighting is off and |
|
| |
| the POD doors are shut. |
|
| |
Exit signs | Visually inspect exit signs for | Every 2 years | Qualified personnel | |
| damage. Replace as necessary. |
|
| |
Emergency egress | Personnel door emergency egress | Every 2 years | Qualified personnel | |
| panic bars. (Visual and |
|
| |
| operational inspection.) |
|
|
Access control
Component to be inspected | Task | Frequency | Capable Party |
|
|
|
|
System functional test | Visual inspection and operational | Annually | Qualified personnel |
| test of door access contact |
|
|
| switches |
|
|
— | Visual inspection and operational | Annually | Qualified personnel |
| test of the following: |
|
|
| • Door access card readers |
|
|
| • Electric strikes |
|
|
| • Door release switches at each |
|
|
| personnel door and/or in |
|
|
| each personnel door panic |
|
|
| bar |
|
|
|
|
|
|
Third-party components
All maintenance for
Examples of external third party components that HP will conduct all manufacturer specified maintenance with a signed SOW includes:
•External UPS equipment
Periodic maintenance 68