HP Performance Optimized Data Center (POD) 40cp manual External panel labels

Models: Performance Optimized Data Center (POD) 40cp

1 79
Download 79 pages 43.3 Kb
Page 9
Image 9

WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with electrical warning labels when operating and maintaining the electrical panels and systems of the HP POD 40c NA.

Front view shown

Item

Component

Description

 

 

 

1

Fire box*

Connection location for fire emergency and VESDAnet signals

2

Demarcation box*

Customer communication connection point:

 

 

ECS

 

 

Security

 

 

Phone

 

 

 

3

415/240V 3-phase, wye,

A feed power for critical IT loads (electrical busways) and house power

 

4-wire, 800 A electrical

 

 

 

panel

 

 

4

415/240V 3-phase, wye,

B feed power for critical IT loads (electrical busways) and house power

 

4-wire, 800 A electrical

 

 

 

panel

 

 

*The demarcation box and the fire box are communication data points that are provided on the POD by HP. Connecting these data points is the responsibility of the customer, unless an approved Statement of Work is initiated.