Fire alarm panel connections

The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP POD 40c NA.

Water specifications

The following table describes the chilled water system specifications for the HP POD 40c NA.

Feature

Specification

 

 

Facility input temperature to the HP POD

12ºC to 24ºC (55ºF to 75ºF)

40c NA

 

Working pressure

1,034 kPa (150 psi)

HP POD 40c NA pressure drop

172.4 kPa (25 psi)

HP POD 40c NA water flow rate

908.5 lpm (240 gpm)

Chilled water supply and return

North America—Two 10.16 cm (4 in) ASME B16.5 class #150

connections

flanges

 

International—Two DIN PN16 DN100 flanges

 

 

Rack specifications

Standard HP POD 40c NA racks (AT978A)

Feature

Specification

 

 

U height

50U

Width

54.6 cm (21.5 in)

Depth

99 cm (39 in)*

Maximum load weight

1,360.7 kg (3,000 lb)

*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.

Thermal and air flow performance

Maximum thermal and air flow

HP POD 40c NA specification

performance parameters

 

 

 

Air temperature—Inlet to rack-mounted

Dependent on IT configuration and chilled water inlet temperature

components)

 

Chilled water temperature

12°C to 24°C (55°F to 75°F)

Total rack-mounted component air flow

Variable as required to maintain the hot aisle setpoint temperature

 

and dependent on IT configuration

Heat rejection capacity

600 kW

Environmental specifications

Feature

Specification

 

 

Operating temperature

-28ºC to 54ºC (-18ºF to 130ºF)