HP Performance Optimized Data Center (POD) 40cp manual Optional features specifications

Models: Performance Optimized Data Center (POD) 40cp

1 79
Download 79 pages 43.3 Kb
Page 72
Image 72

Feature

Specification

 

 

Non-operating temperature*

-29ºC to 54ºC (-20ºF to 130ºF)

 

 

Operating humidity

0% to 100% external

 

10% to 90% non-condensing internal

 

 

Non-operating humidity*

5% to 95% relative non-condensing

 

39ºC (102ºF) maximum wet bulb

 

temperature

 

 

Operating altitude

-76.2 m to 3,048 m (-250 ft to 10,000 ft)

Non-operating altitude

-76.2 m to 9,144 m (-250 ft to 30,000 ft)

*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD 40c NA.

Optional features specifications

Feature

Specification

 

 

Fire suppression

3M Novec 1230 fire extinguishing system provided in two canisters (main and reserve)

 

 

Card reader

12-key pad with 125 KHz proximity and 13.56 MHz contactless smart card

Humidifier

Provides 2-8 lb/hr of water vapor into cold aisle to maintain POD environment within 20%

 

to 80% relative humidity

Specifications 72

Page 72
Image 72
HP Performance Optimized Data Center (POD) 40cp manual Optional features specifications