HP Performance Optimized Data Center (POD) 40cp manual Specifications, General specifications

Models: Performance Optimized Data Center (POD) 40cp

1 79
Download 79 pages 43.3 Kb
Page 70
Image 70

Specifications

General specifications

Features

Specifications

 

 

Overall dimensions

Height—3.66 m (12 ft)

 

Length—12.19 m (40 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—16,783 kg (37,000 lb)

 

Maximum fully loaded—46,266 kg (102,000 lb)

Maximum power2

600 kW HP POD 40c NA

Power input voltage

380 VAC to 415 VAC

 

 

Power distribution3

8 x 200 A electrical busways

Maximum rack quantity

20 racks

RU per rack

50 RU

RU total

1,197 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200 VAC to 240 VAC

Minimum quantity of PDUs per HP POD 40c NA

20 (one per rack)

Maximum quantity of PDUs per HP POD 40c NA

40 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass through fiber

 

Bulk cable pass through copper

 

(Optional) External rated demarcation box

 

 

1The Empty weight includes the HP POD 40c NA structure, empty racks, PDUs, and drop boxes. It does not include IT equipment. All weights are estimates and can vary for your POD.

2Maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c NA is electrically limited to 600 kW.

3Can be configured for redundancy or non-redundancy.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

8

Frequency

60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380 to 415 V

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 70

Page 70
Image 70
HP Performance Optimized Data Center (POD) 40cp manual Specifications, General specifications, Electrical specifications