Specifications
General specifications
Features | Specifications |
|
|
Overall dimensions | • |
| • |
| • |
|
|
Weight1 | |
| Maximum fully |
Maximum power2 | 600 kW HP POD 40c NA |
Power input voltage | 380 VAC to 415 VAC |
|
|
Power distribution3 | 8 x 200 A electrical busways |
Maximum rack quantity | 20 racks |
RU per rack | 50 RU |
RU total | 1,197 RU |
Average capacity per rack (kW) | 30 kW |
Peak rack capacity | 69 kW |
|
|
Voltage to rack | 200 VAC to 240 VAC |
Minimum quantity of PDUs per HP POD 40c NA | 20 (one per rack) |
Maximum quantity of PDUs per HP POD 40c NA | 40 (two per rack) |
Maximum power per PDU | 30A = 17 kW; 60A = 34 kW |
Network supported | Bulk cable pass through fiber |
| Bulk cable pass through copper |
| (Optional) External rated demarcation box |
|
|
1The Empty weight includes the HP POD 40c NA structure, empty racks, PDUs, and drop boxes. It does not include IT equipment. All weights are estimates and can vary for your POD.
2Maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c NA is electrically limited to 600 kW.
3Can be configured for redundancy or
Electrical specifications
Electrical busway system information
Feature | Specification |
|
|
Number of busways | 8 |
Frequency | 60 Hz |
Amps (per busway) | 200 A |
Voltage (per busway) | 380 to 415 V |
Grounding | Copper |
Busway configuration |
Specifications 70