HP Performance Optimized Data Center (POD) 40cp manual Removing the cold aisle temperature sensor

Models: Performance Optimized Data Center (POD) 40cp

1 79
Download 79 pages 43.3 Kb
Page 55
Image 55

Removing the cold aisle temperature sensor

1.Remove the two screws that secure the sensor cover (1), and then remove the cover (2).

2.Cut the two red wires inside the sensor box.

3.For each of the five clamps securing the sensor tube to the HP POD 40c NA structure, remove the screw that secures the clamp (1), rotate the clamp (2), and then pull the clamp out to remove the clamp (3).

4.Remove the sensor tube.

Removal and replacement procedures 55