Input Specifications

Table C-2: Input Specifications

 

 

Default

Available

 

 

 

Settings

 

 

Utility Voltage

Settings

Power Cord

UPS Model

Nominal

Frequency (Hz)

Utility Voltage

Supplied

 

Voltage

 

 

(VAC)

 

 

 

(VAC)

 

 

 

 

 

 

 

 

 

 

R1500 XR NA

50/60

120

110, 120, 1271

Non-detachable

 

 

 

 

power cord with

 

 

 

 

NEMA 5-15 plug

 

 

 

 

 

R1500 XR JPN

50/60

100

1002

Non-detachable

 

 

 

 

power cord with

 

 

 

 

NEMA 5-20 plug

 

 

 

 

 

R1500 XR H INT’L

50/60

230

220, 230, 240

Input power

 

 

 

 

receptacle

 

 

 

 

(IEC-320-C14) for

country-specific plug attachment

Note: 1 120 on battery

2110 on battery

Before connecting devices, verify that the UPS will not overload by checking that the rating of the devices does not exceed the capacity of the UPS. Evenly distribute connected devices throughout all load segments. Do not exceed the rating of individual receptacles. Connect devices according to shutdown preference.

After checking that the UPS will not overload, connect the power cords from the devices to the appropriate output receptacles of the UPS.

WARNING: To prevent risk of personal injury from electric shock, the

UPS R1500 XR H INT’L model is not suitable for installation where the total earth (ground) conductor leakage current for all connected devices exceeds 3.5 mA. Use RackBuilder Pro (obtainable at www.hp.com) to find the total system leakage current.

C-2

HP Uninterruptible Power System R1500 XR Models User Guide