Battery Maintenance
Determining When to Replace Batteries
When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be replaced within 30 to 60 days.
1 |
1 |
100%
25%
Figure 4-1. Bad Battery/Low Battery LED
To check a battery alarm, initiate a UPS battery
NOTE: Depending on usage and environmental conditions, the batteries should last three to six years.
For more information on initiating a
Obtaining New Batteries
New batteries may be required within 30 to 60 days when the Bad Battery/Low Battery LED illuminates red. Obtain spare batteries for the UPS when this occurs.
HP supplies spare battery packs for this UPS. The UPS spare battery kit part number is
CAUTION: Because of the short shelf life of the battery, avoid storing a battery spare as a backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep these batteries charged while in storage is implemented.
HP Uninterruptible Power System R1500 XR Models User Guide |