Specifications

Battery Specifications

Table C-5: Battery Specifications

Feature

Specification

Type

Sealed lead-acid; maintenance-free

 

 

Voltage

48 V Battery String

 

 

Charging

HP recommends 24 hours to allow full charge

 

 

 

Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load

 

 

Environmental Specifications

Table C-6: Environmental Specifications

Feature

Specification

Operating temperature

10oC to 40oC (50oF to 104oF)

 

UL-tested at 25oC (77oF)

 

 

Non-operating temperature

0oC to 25oC (32oF to 77oF)

 

 

Operating humidity

20% to 80% relative humidity (non-condensing)

 

 

Non-operating humidity

5% to 95% relative humidity (non-condensing);

 

38.7 oC (101.7oF) maximum wet bulb temperature with no

 

cosmetic damage

 

 

Operating altitude

Up to 2,000 meters (6,562 feet) above sea level

 

 

Non-operating altitude

Up to 9,144 meters (30,000 feet) above sea level

 

 

Audible noise

Less than 46 dBA

 

 