Battery Maintenance

Replacing Batteries

There are two options for replacing UPS batteries:

Powering down the UPS before removing the batteries

In certain circumstances, replacing the batteries without powering down the UPS

CAUTION: While replacing the batteries without powering down the UPS, the UPS is not protected in the event of a utility power failure.

Preparing the UPS

Batteries can be replaced without powering down the UPS if the UPS is not supplying battery power to devices (utility is present, indicating that the UPS is supplying utility power).

To replace batteries with the UPS powered down:

1.Shut down all load devices.

2.Press the Standby button to take the UPS out of Operate mode.

3.Disconnect the UPS from utility power.

4.Wait at least 60 seconds while the UPS internal circuitry discharges.

Removing the Battery Pack

To remove the battery pack:

1. Remove the UPS front bezel by pulling on both ends (1).

1

Figure 4-2: Removing the UPS front bezel

HP Uninterruptible Power System R1500 XR Models User Guide

4-3