Battery Maintenance
Replacing Batteries
There are two options for replacing UPS batteries:
•Powering down the UPS before removing the batteries
•In certain circumstances, replacing the batteries without powering down the UPS
CAUTION: While replacing the batteries without powering down the UPS, the UPS is not protected in the event of a utility power failure.
Preparing the UPS
Batteries can be replaced without powering down the UPS if the UPS is not supplying battery power to devices (utility is present, indicating that the UPS is supplying utility power).
To replace batteries with the UPS powered down:
1.Shut down all load devices.
2.Press the Standby button to take the UPS out of Operate mode.
3.Disconnect the UPS from utility power.
4.Wait at least 60 seconds while the UPS internal circuitry discharges.
Removing the Battery Pack
To remove the battery pack:
1. Remove the UPS front bezel by pulling on both ends (1).
1
Figure 4-2: Removing the UPS front bezel