Configuration

2.To advance to the appropriate voltage configuration (to the right), press the On button (3). The selected voltage configuration LED flashes. Activate the voltage configuration by pressing the Standby button (2). The previously selected configuration parameter LED turns off.

NOTE: Only one nominal utility voltage can be configured. When setting voltage configuration parameters, selecting an On value for any one parameter automatically sets the other three possibilities to Off.

3.To toggle the Site Wiring Fault option from active to inactive, press the On button (3) to advance to the Site Wiring Fault LED, then press the Standby button (2).

4.To accept the configuration settings and exit Configure mode, press the Test/Alarm Reset button (1).

NOTE: If the unit remains idle for two minutes, Configure mode times out and the configuration settings are not stored.

3-4

HP Uninterruptible Power System R1500 XR Models User Guide