3LOW VOLTAGE CONNECTIONS

3LOW VOLTAGE CONNECTIONS

4HIGH VOLTAGE POWER SUPPLY CONNECTIONSManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background C

A

CUTOUT WITH

GROMMET

 

24V CONTROL WIRES B

HIGH VOLTAGE FIELD WIRING

LOW VOLTAGE (24V) FIELD WIRING

 

 

 

 

 

 

 

 

 

WIRE RUN LENGTH

AWG# INSULATION TYPE

 

 

 

 

LESS THAN 100’ (30 METERS)

18

TEMPERATURE RATING

 

 

 

MORE THAN 100’ (30 METERS)

16

35ºC MINIMUM.

 

 

 

 

 

 

 

 

NOTE − For proper voltages, select thermostat wire (control wires) gauge per table above.

NOTE − Do not bundle any excess 24VAC control wires inside control box.

ARun 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie.

C Make 24VAC control wire connections.

DTighten wire tie to security 24V control wiring.

NOTE − Wire tie provides low voltage wire strain relief and to maintain separation of field installed low and high voltage circuits.

DTIGHTEN WIRE TIE

Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See figures 14 and 15 for typical field connections when connecting unit to either a CBX32MV or CBX40UHV in non−communicating mode. For connections to other Lennox air handlers or furnaces, see the ComfortSense® 7000 installation instruction for further match component wiring illustrations.

4HIGH VOLTAGE POWER SUPPLY CONNECTIONS

OUTDOOR UNIT

CONTROL BOX

GROUND

NOTE − Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring.

NOTE − To facilitate a conduit, a cutout is lo- cated in the bottom of the control box. Connect conduit to the control box using a proper con- duit fitting.

G

L1 L2

CONDUIT

CUTOUT

CONDUIT