APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND

ADD CHARGE VALUES

Listed below are the approved matched system components (air handlers and indoor coils), targeted subcooling and add charge values for the XP16. This information is also listed on the unit charging sticker located on the outdoor unit access panel.

Subcooling values listed in the following tables are based on outdoor ambient air temperature of:

S60°F (15.5°C) and above for cooling mode

S59°F (15.0°C) and below for heating mode.

Table 3. XP16−024−230

 

Heating

Cooling

 

 

Indoor Air Handers

Mode

Mode

*Add Charge

+5ºF

+1ºF

 

 

and Coils

 

 

 

 

 

 

 

Subcooling

lb.

oz.

 

 

 

 

 

CBX26UH−024

45

6

0

15

 

 

 

 

 

CBX27UH−024−230

20

7

0

9

 

 

 

 

 

CBX27UH−030−230

17

7

1

3

 

 

 

 

 

CBX32MV−024/030

20

7

0

9

 

 

 

 

 

CBX32MV−036

17

7

1

3

 

 

 

 

 

CBX40UHV−024

17

7

1

3

 

 

 

 

 

CBX40UHV−030

17

7

1

3

 

 

 

 

 

CBX40UHV−036

17

7

1

3

 

 

 

 

 

CH33−31B

31

8

1

12

 

 

 

 

 

CR33−30/36A/B/C

45

4

0

0

 

 

 

 

 

CX34−31A/B

24

7

1

11

 

 

 

 

 

CX34−38A/B

18

8

1

10

 

 

 

 

 

Table 4. XP16−036−230

 

 

 

 

 

 

 

 

Heating

Cooling

 

 

Indoor Air Handers

Mode

Mode

*Add Charge

+5ºF

+1ºF

 

 

and Coils

 

 

 

 

 

 

 

Subcooling

lbs.

oz.

 

 

 

 

 

CBX26UH−036

50

5

0

0

 

 

 

 

 

CBX27UH−036−230

22

7

0

9

 

 

 

 

 

CBX27UH−042−230

24

11

3

0

 

 

 

 

 

CBX32M−036

22

7

0

9

 

 

 

 

 

CBX32MV−036

22

7

0

9

 

 

 

 

 

CBX32MV−048

24

11

3

0

 

 

 

 

 

CBX40UHV−030

22

7

0

9

 

 

 

 

 

CBX40UHV−036

22

7

0

9

 

 

 

 

 

CBX40UHV−042

24

11

3

0

 

 

 

 

 

CBX40UHV−048

24

11

3

0

 

 

 

 

 

CH33−43B

13

10

2

7

 

 

 

 

 

CH33−48C

37

11

2

11

 

 

 

 

 

CH33−43C

37

11

2

11

 

 

 

 

 

CR33−48B/C

49

7

0

9

 

 

 

 

 

CX34−43B/C

29

9

2

11

 

 

 

 

 

CX34−50/60C

29

9

2

11

 

 

 

 

 

Table 5. XP16−048−230

 

Heating

Cooling

 

 

Indoor Air Handers

Mode

Mode

*Add Charge

+5ºF

+1ºF

 

 

and Coils

 

 

 

 

 

 

 

Subcooling

lbs.

oz.

 

 

 

 

 

CBX26UH−048−230

10

8

1

4

 

 

 

 

 

CBX27UH−048−230

19

9

1

4

 

 

 

 

 

CBX27UH−060−230

13

14

3

3

 

 

 

 

 

CBX32M−048

19

9

1

4

 

 

 

 

 

CBX32M−060

14

9

1

11

 

 

 

 

 

CBX32MV−048

19

9

1

4

 

 

 

 

 

CBX32MV−060

14

9

1

11

 

 

 

 

 

CBX32MV−068

9

8

1

11

 

 

 

 

 

CBX40UHV−048

19

9

1

4

 

 

 

 

 

CBX40UHV−060

14

9

1

11

 

 

 

 

 

CH23−68

24

10

1

12

 

 

 

 

 

CH33−49C

19

9

2

5

 

 

 

 

 

CH33−50/60C

19

9

2

5

 

 

 

 

 

CH33−60D

13

8

0

0

 

 

 

 

 

CH33−62D

11

9

1

4

 

 

 

 

 

CR33−50/60C

15

7

0

10

 

 

 

 

 

CR33−60D

15

7

0

10

 

 

 

 

 

CX34−60D

14

8

1

0

 

 

 

 

 

CX34−62D

9

9

1

6

 

 

 

 

 

CX34−62C

8

9

1

9

 

 

 

 

 

Table 6. XP16−060−230

 

 

 

Heating

Cooling

 

 

Indoor Air Handers

Mode

Mode

*Add Charge

+5ºF

+1ºF

 

 

and Coils

 

 

 

 

 

 

 

Subcooling

lbs.

oz.

 

 

 

 

 

CBX26UH−060

20

9

4

13

 

 

 

 

 

CBX27UH−060−230

10

6

2

3

 

 

 

 

 

CBX32M−060

17

6

1

12

 

 

 

 

 

CBX32MV−060

17

6

1

12

 

 

 

 

 

CBX32MV−068

15

7

2

1

 

 

 

 

 

CBX40UHV−060

17

6

1

12

 

 

 

 

 

CH23−682

37

9

2

10

 

 

 

 

 

CH33−50/60C

33

8

1

0

 

 

 

 

 

CH33−62D

15

7

1

4

 

 

 

 

 

CR33−50/60C

24

7

0

0

 

 

 

 

 

CR33−60D

24

7

0

0

 

 

 

 

 

CX34−62C

21

9

2

16

 

 

 

 

 

CX34−62D

13

7

1

4

 

 

 

 

 

*Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)