Lenox Elite Series XP16 Units Heat Pumps, P506640-01 Test, O Line Status, If in COOLING Mode

Models: Elite Series XP16 Units Heat Pumps P506640-01

1 43
Download 43 pages 56.47 Kb
Page 39
Image 39
TEST

TEST

Placing the jumper on the field test pins (P1) allows the technician to:

S S S S

Clear short cycle lockout

Clear five−strike fault lockout

Cycle the unit in and out of defrost mode

Place the unit in defrost mode to clear the coil

When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.

The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.

Y1 Active

Place a jumper on TEST pins for longer than one second but less than two seconds.

Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.

Place a jumper on TEST pins for more than two seconds.

Clears any short cycle lockout and five strike fault lockout function, if applicable.

ACTIVE

O Line Status

INACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

If in COOLING Mode

If in DEFROST Mode

If in HEATING Mode

No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.

The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 45 minute test.

If no ambient or coil sensor fault exist, unit will go into DEFROST MODE.

If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.

NOTE Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.

If jumper on TEST pins remains in place for more than five seconds.

The unit will return to HEAT MODE un−calibrated with defrost timer set for 34 minutes.

If jumper on TEST pins is removed before a maximum of five seconds.

The unit will remain in DEFROST MODE until termination on time or temperature.

Figure 27. Test Pin (P1) Functions

Page 39

XP16 SERIES

Page 39
Image 39
Lenox Elite Series XP16 Units Heat Pumps Test, O Line Status, If in COOLING Mode, If in DEFROST Mode, If in HEATING Mode