DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE

DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE

Occurs after power up and cooling operation, or if the coil temperature exceeds

the termination temperature while in Heat Mode.

Demand defrost control defaults to 30 minute ime / Temperature Mode

Reset Compressor Runtime / Reset Three / Five Strike Counter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEMAND MODE

 

THIRTY (30) MINUTE TIME /

 

45 MINUTE

 

 

 

Accumulate compressor runtime of

 

TEMPERATURE MODE

 

TIME/TEMPERATURE MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

more than 30 minutes while coil

 

Accumulate compressor runtime

 

Accumulate compressor runtime

 

 

 

temperature is below 35° F (2°C).

 

while coil temperature is below 35° F

 

while coil temperature is below 35°

 

 

 

When the accumulated compressor

 

(2°C). When the accumulated

 

F (2°C). When the accumulated

 

 

 

time exceeds six (6) hours or if the

 

compressor time exceeds 30 minutes

 

compressor time exceeds 45

 

 

 

coil sensor indicates frost is present

 

go to Defrost.

 

minutes go to Defrost.

 

 

 

on coil, go to Defrost.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

SOutdoor Fan OFF

SReversing Valve ON

SW1 line ON

Monitor coil temperature and

time in defrost mode.

HOW DID DEFROST TERMINATE?

Coil temperature was above 35°F (2°C) for four (4) minutes. of the 14−minute defrost OR reached defrost termination temperature.

DEFROST TERMINATION

SCompressor runtime counter RESET

SOutdoor Fan ON

SReversing Valve OFF

SW1 line OFF

Defrosted for 14−minute without the coil temperature going above 35°F (2°C) for four (4) minutes and coil did not reach termination temperature.

DEFROST TERMINATION

SCompressor runtime counter RESET

SOutdoor Fan ON

S Reversing Valve OFF

SW1 line OFF

Attempt to Calibration emperature measurements are not taken for the first few minutes of each heat demand. This is

to allow coil temperatures to stabilize. demand defrost control has a maximum of 20 minutes of accumulated compressor runtime in heat mode to calibrate demand defrost control This may involve more than one heating demand.

YES

Was stable coil temperature attained within 20 minutes?

NO Demand defrost control reverts to 45 minute time / temperature.

Figure 26. Defrost Calibration